Environmental conditions to EN 61131-2
Horizontal installation lying
EN 61131-2
0…+60°C
Vertical installation
EN 61131-2
0…+60°C
Air humidity
EN 60068-2-30
RH1 (without condensation, rel. humidity 10…95%)
Pollution
EN 61131-2
Degree of pollution 2
Installation altitude max.
-
2000m
Mechanical
Oscillation
EN 60068-2-6
1g, 9Hz ... 150Hz
Shock
EN 60068-2-27
15g, 11ms
Mounting conditions
Mounting place
-
In the control cabinet
Mounting position
-
Horizontal and vertical
EMC
Standard
Comment
Emitted interference
EN 61000-6-4
Class A (Industrial area)
Noise immunity
zone B
EN 61000-6-2
Industrial area
EN 61000-4-2
ESD
8kV at air discharge (degree of severity 3),
4kV at contact discharge (degree of severity 2)
EN 61000-4-3
HF field immunity (casing)
80MHz … 1000MHz, 10V/m, 80% AM (1kHz)
1.4GHz ... 2.0GHz, 3V/m, 80% AM (1kHz)
2GHz ... 2.7GHz, 1V/m, 80% AM (1kHz)
EN 61000-4-6
HF conducted
150kHz … 80MHz, 10V, 80% AM (1kHz)
EN 61000-4-4
Burst, degree of severity 3
EN 61000-4-5
Surge, degree of severity 3 *
*) Due to the high-energetic single pulses with Surge an appropriate external protective circuit with lightning protection elements like conductors for lightning and overvoltage is
necessary.
VIPA System MICRO
Basics and mounting
General data
HB400 | CPU | M13-CCF0000 | en | 16-47
32
Содержание VIPA System MICRO M13-CCF0000
Страница 35: ...3 2 2 Interfaces VIPA System MICRO Hardware description Structure Interfaces HB400 CPU M13 CCF0000 en 16 47 35 ...
Страница 211: ...Appendix VIPA System MICRO Appendix HB400 CPU M13 CCF0000 en 16 47 211 ...
Страница 212: ...Content A System specific event IDs B Integrated blocks VIPA System MICRO Appendix HB400 CPU M13 CCF0000 en 16 47 212 ...