9.6.5.2
Parametrization in SPEED7 Studio
9.6.5.2.1 ‘I/O addresses’
Sub module
Input address
Access
Assignment
Count
816
DINT
Channel 0: Counter value / Frequency value
820
DINT
Channel 1: Counter value / Frequency value
824
DINT
Channel 2: Counter value / Frequency value
828
DINT
Channel 3: Counter value / Frequency value
9.6.5.2.2 Basic parameters
Via
‘Basic parameters’
you can reach
‘Select interrupt’
. Here you can define the inter-
rupts the CPU will trigger. The following parameters are supported:
n
None: The interrupt function is disabled.
n
Process: The following events of the counter can trigger a hardware interrupt (select-
able via
‘Count’
):
–
Hardware gate opening
–
Hardware gate closing
–
On reaching the comparator
–
on Counting pulse
–
on overflow
–
on underflow
n
Diagprocess: A diagnostics interrupt is only triggered when a hardware inter-
rupt was lost.
9.6.5.2.3 ‘Channel x’
Select via
‘Channel’
the channel select via
‘Operating’
the counter operating mode. The
following counter operating modes are supported:
n
Not parametrized: Channel is de-activated
n
Count endless
n
Count once
n
Count periodical
Counter
Default values and structure of this dialog box depend on the selected
‘Operating mode’
.
Select interrupt
Operating mode
Operating mode
VIPA System MICRO
Configuration with VIPA SPEED7 Studio
Deployment I/O periphery > Counter
HB400 | CPU | M13-CCF0000 | en | 16-47