Wiring Main Circuit Terminals
2-
15
Standard Connection Diagrams
Standard Inverter connection diagrams are shown in
Fig 2.5.
These are the same for both 200 V Class and
400 V Class Inverters. The connections depend on the Inverter capacity.
Control power is supplied internally from the main circuit DC power supply for all Inverter models.
Fig 2.5 Main Circuit Terminal Connections
CIMR-G7B20P4 to 2015 and 40P4 to
4015
Be sure to remove the short-circuit bar before connecting the DC
reactor.
CIMR-G7B2018, 2022, and 4018 to 4045
The DC reactor is built in.
IMPORTANT
When connecting a separately-installed type Braking Unit (model CDBR), connect the B1 terminal of the
Inverter to the + terminal of the Braking Unit and connect the
−
terminal of the Inverter to the
−
terminal of the
Braking Unit. The B2 terminal is not used in this case.
CIMR-G7B2030 to 2110
CIMR-G7B4055 to 4300
IMPORTANT
If a Braking Unit or a Braking Resistor Unit is connected to a wrong terminal, the Inverter, Braking Unit, or
Braking Resistor Unit can be damaged.
+ 1 + 2 B1 B2
R/L1
S/L2
T/L3
U/T1
V/T2
IM
W/T3
DC reactor
(optional)
3-phase 200
VAC (400 VAC)
Braking Resistor
Unit (optional)
+ 1
+ 3
R/L1
S/L2
T/L3
U/T1
V/T2
IM
W/T3
R1/L11
S1/L21
T1/L31
Braking Unit
(optional)
Braking Resistor
Unit (optional)
3-phase 200
VAC (400 VAC)
+ 1
+ 3
R/L1
S/L2
T/L3
U/T1
V/T2
IM
W/T3
R1/L11
S1/L21
T1/L31
/
l
2
r/
l
1
3-phase
200 VAC
Braking Unit
(optional)
Braking Resistor
Unit (optional)
+ 1
+ 3
R/L1
S/L2
T/L3
U/T1
V/T2
IM
W/T3
R1/L11
S1/L21
T1/L31
200/
l
2
200
400/
l
2
400
r/
l
1
3-phase
400 VAC
Braking Unit
(optional)
Braking Resistor
Unit (optional)