Setting Precautions
To switch command inputs between the Communications Option Board and the control circuit terminals, set
the following constants.
•
Set b1-01 (Reference Selection) to 1 [Control circuit terminal (analog input)]
•
Set b1-02 (Operation Method Selection to 1 [Control circuit terminal (sequence inputs)]
•
Set one of the constants H1-01 to H1-10 (multi-function contact input terminal S3 to S12 function selec-
tion) to 2 (Option/Inverter selection).
Jog Frequency Operation without Forward and Reverse Commands
(FJOG/RJOG)
The FJOG/RJOG command functions operate the Inverter using jog frequencies by using the terminal ON/
OFF operation. When using the FJOG/RJOG commands, there is no need to input the Run Command.
To use this function, set one of the constants H1-01 to H1-10 (multi-function contact input terminal S3 to S12
function selection) to 12 (FJOG command) or 13 (RJOG command).
Related Constants
Note The unit is set in o1-03 (Frequency units of reference setting and monitor). The default for o1-03 is 0 (increments of 0.01 Hz).
* The setting range for open-loop vector 2 control is 0 to 132.0.
Multi-Function Contact Inputs (H1-01 to H1-10)
Application Precautions
•
Jog frequencies using FJOG and RJOG commands are given priority over other frequency references.
•
When both FJOG command and RJOG commands are ON for 500 ms or longer at the same time, the
Inverter stops according to the setting in b1-03 (stopping method selection).
Terminal Status
Frequency Reference and Run Command Selection
OFF
Inverter
(Can be operated from frequency reference or control circuit terminal from analog input termi-
nal.)
ON
Communications Option Board
(Frequency reference and Run Command are enabled from Communications Option Board.)
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
d1-17
Jog frequency
reference
The frequency reference when the
jog frequency reference selec-
tion, FJOG command, or RJOG
command is ON.
0 to
400.00
*
6.00
Hz
Yes
Q
Q
Q
Q
Q
292H
点动频率上限
Set-
ting
Value
Function
Control Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
12
FJOG command (ON: Forward run at jog frequency d1-17)
Yes
Yes
Yes
Yes
Yes
13
RJOG command (ON: Reverse run at jog frequency d1-17)
Yes
Yes
Yes
Yes
Yes