Digital Operation Display Functions and Levels
5-
5
C6-11
Carrier fre-
quency for
open-loop
vector 2
control
Select carrier frequency when open-
loop vector 2 control is used.
1: 2kHz
2: 4kHz
3: 6kHz
4: 8kHz
1 to 4
1
*2
No
No
*13
No
*13
No
*13
No
*13
Q
22DH
无 PG 矢量
2 载波
d1-01
Frequency
reference 1
Set the frequency reference in the unit
specified in o1-03 (Frequency Units
for Reference Setting And Monitor,
default: Hz)
0 to
400.00
*7
0.00 Hz
Yes
Q
Q
Q
Q
Q
280H
频率指令 1
d1-02
Frequency
reference 2
Frequency reference when multi-step
speed reference 1 is ON for a multi-
function input (unit: Set in o1-03).
0.00 Hz
Yes
Q
Q
Q
Q
Q
281H
频率指令 2
d1-03
Frequency
reference 3
Frequency reference when multi-step
speed reference 2 is ON for a multi-
function input (unit: Set in o1-03).
0.00 Hz
Yes
Q
Q
Q
Q
Q
282H
频率指令 3
d1-04
Frequency
reference 4
Frequency reference when multi-step
speed reference 1 and 2 are ON for a
multi-function input (unit: Set in o1-
03).
0.00 Hz
Yes
Q
Q
Q
Q
Q
283H
频率指令 4
d1-17
Jog
frequency
reference
Frequency reference when Jog Fre-
quency Selection, FJOG command, or
RJOG command is ON for a multi-
function input (unit: Set in o1-03).
6.00 Hz
Yes
Q
Q
Q
Q
Q
292H
点动频率上
限
E1-01
Input volt-
age setting
Set the Inverter input voltage in 1 volt.
This set value will be the basis for the
protection functions.
155 to
255
*3
200 V
*3
No
Q
Q
Q
Q
Q
300H
输入电压
E1-03
V/f pattern
selection
0 to E: Select from 15 preset patterns.
F: Custom user-set patterns (Applica-
ble for setting E1-04 to E1-10).
0 to F
F
No
Q
Q
No
No
No
302H
V/F 曲线设
定
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
-loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2