5
-34
* 1. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
* 2. The factory setting will change when the control method is changed. The open-loop vector 1 factory settings are given.
* 3. E1-11 and E1-12 are disregarded when set to 0.0.
* 4. E1-13 is set to the same value as E1-05 by autotuning.
* 5. The setting range for open-loop vector 2 control is 0 to 132.0.
Motor Setup: E2
User constants for motor 1 are shown in the following table.
E1-11
Mid. output
frequency 2
Set only to fine-adjust V/f for the
output range. Normally, this setting
is not required.
0.0 to
400.0
*5
0.0 Hz
*3
No
A
A
A
A
A
30AH 6-120
中间频率 2
E1-12
Mid. output
frequency
voltage 2
0.0 to
255.0
*1
0.0 V
*3
No
A
A
A
A
A
30BH 6-120
中间电压 2
E1-13
Base
voltage
0.0 to
255.0
*1
0.0 V
*4
No
A
A
Q
Q
Q
30CH 6-120
基本电压
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
E2-01
Motor rated
current
Sets the motor rated current in
1 A units.
These set values will become
the reference values for motor
protection, torque limits and
torque control.
This constant is automatically
set during autotuning.
0.32 to
6.40
*2
1.90 A
*1
No
Q
Q
Q
Q
Q
30EH
4-5
6-57
6-117
电机额定电流
E2-02
Motor rated
slip
Sets the motor rated slip in
Hz units.
These set values will become
the reference values for slip
compensation.
This constant is automatically
set during autotuning.
0.00 to
20.00
2.90 Hz
*1
No
A
A
A
A
A
30FH
6-115
6-117
电机额定滑差
E2-03
Motor no-
load current
Sets the motor no-load cur-
rent in 1 A units.
This constant is automatically
set during autotuning.
0.00 to
1.89
*3
1.20 A
*1
No
A
A
A
A
A
310H
6-117
空载电流
E2-04
Number of
motor poles
Sets the number of motor
poles.
This constant is automatically
set during autotuning.
2 to 48 4 poles
No
No
Q
No
Q
Q
311H
6-117
电机极数
E2-05
Motor line-
to-line resis-
tance
Sets the motor phase-to-phase
resistance in
Ω
units.
This constant is automatically
set during autotuning.
0.000
to
65.000
9.842
Ω
*1
No
A
A
A
A
A
312H
6-117
线间电阻
E2-06
Motor leak
inductance
Sets the voltage drop due to
motor leakage inductance as a
percentage of the motor rated
voltage.
This constant is automatically
set during autotuning.
0.0 to
40.0
18.2%
*1
No
No
No
A
A
A
313H
6-117
电机漏电感
Con-
stant
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2