8 Object Dictionary
YASKAWA EUROPE GMBH
YEU SIEP C710616 86A - AC Drive A1000 Option Powerlink - Technical Manual
25
20D0 (Hex) - FM analog output 1
This object controls the FM analog output value.
20E0 (Hex) - AM analog output 2
This object controls the AM analog output value.
20F0 (Hex) - Multi-function DO output
This object controls the multi-function DO outputs.
2100 (Hex)/2101 (Hex) - Drive Status
These objects can be used to monitor the drive status. The value in object 2100 (Hex) is not filtered.
2110 (Hex) - Output Frequency
This object can be used to monitor the drive output frequency. The unit of the monitor value is determined by drive parameter o1-03 (0 = Hz; 1 = %
with 100% equals parameter E1-04; 2 = rev/min with the motor poles number entered into E2-04/E4/04/E5-04; 3 = user defined parameters o1-10
and 01-11.
The value will be used as the speed reference for speed control (d5-01 = 0) or as the speed limit in torque control (d5-01 = 1).
2120 (Hex) - Output Current
This object can be used to monitor the drive output current in units of Ampere. The current value resolution is the same as in drive monitor U1-03
(for details refer to the technical manual of the drive).
Index (Hex.)
Subindex
Content
Access
PDO Mapping
Data Length
20D0
1
Value
Read/Write
Rx Tx
-
2
MEMOBUS/Modbus register address
Read Only
No
-
Index (Hex.)
Subindex
Content
Access
PDO Mapping
Data Length
20E0
1
Value
Read/Write
Rx Tx
-
2
MEMOBUS/Modbus register address
Read Only
No
-
Index (Hex.)
Subindex
Content
Access
PDO Mapping
Data Length
20F0
1
Value
Read/Write
Rx Tx
-
2
MEMOBUS/Modbus register address
Read Only
No
-
Index (Hex)
Subindex
Content
Default
Access
PDO Mapping Data Length Update Cycle
2100
0
Number of entries
-
Read Only
Possible
2 byte
2 ms
1
Value
-
Read Only
Tx
2 byte
2 ms
2
MEMOBUS/Modbus register address
00FC (Hex)
Read Only
No
2 byte
-
Bit No. (Hex)
Function
Description
0
During Run
1: During Run 0: During Stop
1
During Zero Speed
1: During Zero Speed
2
Reverse Running
1: During Reverse Running 0: During Forward Running
3
During Fault Reset Signal Input
1: During Fault Reset Signal Input
4
During Speed Agree
1: During Speed Agree
5
During Drive Ready
1: During Drive Ready 0: Not Ready
6
During Alarm
1: During Alarm
7
During Fault
1: During Fault
8
During Operation Error
1: During Operation Error
9
During Momentary Power Loss
1: During Momentary Power Loss 0: During Power Loss
A
NetCtrl Status
1: NetCtrl
B
Digital Output 1 Status (function set in drive parameter H2-01)
1: ON 0: OFF
C
Digital Output 2 Status (function set in drive parameter H2-02)
1: ON 0: OFF
D
Digital Output 3 Status (function set in drive parameter H2-03)
1: ON 0: OFF
E
Motor 2 Selected
1: Motor 2 Selected
F
Zero-Servo End
1: Zero-Servo End
Index (Hex)
Subindex
Content
Default
Access
PDO Mapping Data Length Update Cycle
2110
0
Number of entries
-
Read Only
-
-
1
Value
-
Read Only
Tx
Unsigned 16
2
MEMOBUS/Modbus register address
0041 (Hex)
Read Only
No
Unsigned 16
Index (Hex)
Subindex
Content
Default
Access
PDO Mapping
Value Range
2120
0
Number of entries
-
Read Only
-
-
1
Value
-
Read Only
Tx
Unsigned 16
2
MEMOBUS/Modbus register address
00FB (Hex)
Read Only
No
Unsigned 16