8 Object Dictionary
20
YASKAWA EUROPE GMBH
YEU SIEP C710616 86A - AC Drive A1000 Option Powerlink - Technical Manual
1003 (Hex) - Pre-defined Error Field
This register provides a history of errors that occurred in the drive and have been signalized via the Emergency object. Subindex 0 contains the
number of errors. Subindexes 1 to FF contain a rolling list of error codes where subindex 1 always contains the last occurring error.
Powerlink Option Card Error Codes on page 36
for a list of possible error codes. The number of valid logged errors in sub index is 0x01-0xFE.
Writing a 0 to subindex 0 resets the error field.
1006 (Hex) - NMT Cycle Time
This object contains the Powerlink communication cycle time interval.
1008 (Hex) - Manufacturer Device Name
This object contains the manufacturer device name. String: Powerlink
for 1000 series.
1009 (Hex) - Manufacturer Hardware Version
This object contains the manufacturer hardware version.
Value: 1.x
x = HW revision assigned during production
100A (Hex) - Manufacturer Software Version
This object contains the Manufacturer software version.
Value: VST92x101
Note:
The complete Software Version is available via 1018 (Hex), subindex 3.
Refer to 1018 (Hex) - Identity Object on page 20
1018 (Hex) - Identity Object
This object contains general information about the drive.
1020 (Hex) - Device Local Configuration Date and Time
This object contains configuration information about the drive.
Index (Hex)
Subindex
Content
Access
PDO Mapping
Value Range
1003
0
Number of errors
Read/Write
No
Unsigned 8
1
Standard error field
Read Only
Unsigned 32
Index (Hex)
Subindex
Content
Access
PDO Mapping
Value Range
1006
–
NMT Cycle Time
Read/Write
No
Unsigned 32
Index (Hex)
Subindex
Content
Access
PDO Mapping
Value Range
1008
–
Manufacturer device name
Read Only
No
Visible string
Index (Hex)
Subindex
Content
Access
PDO Mapping
Value Range
1009
–
Manufacturer hardware version
Read Only
No
Visible string
Index (Hex)
Subindex
Content
Access
PDO Mapping
Value Range
100A
–
Manufacturer software version
Read Only
No
Visible string
Index (Hex)
Subindex
Content
Access
PDO Mapping
Value
Value Range
1018
-
Identity object
Read/Write
-
Unsigned 32
0
Number of entries
Read Only
No
4
Unsigned 8
1
YASKAWA ETG Member Vendor ID
Read Only
No
0x010000E7
(Yaskawa Electric)
Unsigned 32
2
Powerlink
option product code
Read Only
No
0x53454C33
(ASCII: SEL3)
Unsigned 32
3
YASKAWA Powerlink
option software revision
number
Read Only
No
9243.xxyy
Unsigned 32
4
Powerlink option serial number
Read Only
No
Unsigned 32
Index (Hex)
Subindex
Content
Access
PDO Mapping
Value
Value Range
1020
-
Device local configuration date and time
-
-
-
0
Number of entries
Read Only
No
2
Unsigned 8
1
Configuration Date in Days
Read/Write
No
Unsigned 32
2
Configuration Time in ms
Read/Write
No
Unsigned 32