5 Installation Procedure
YASKAWA EUROPE GMBH
YEU SIEP C710616 86A - AC Drive A1000 Option Powerlink - Technical Manual
11
Prior to Installing the Option Card
Prior to installing the Powerlink Option, wire the drive and make necessary connections to the drive terminals. For more information on wiring and
connecting the drive, refer to the manual packaged with the drive. Verify that the drive runs normally without the option installed.
Installing the Option
1.
Shut off power to the drive, wait the appropriate amount of time for voltage to dissipate, then remove the operator (9) and front cover (11).
Refer to the drive manual for direction on removing the front cover.
2.
Insert the CN5 connector on the option (5) into the CN5-A connector on the drive (3), then fasten it into place using one of the screws
included with the option.
Connect the ground wire (7) to the ground terminal (4) using one of the screws provided with the option.
Note:
There are only two screw holes on the drive for ground terminals. If three option cards are connected, two of the ground wires will need to share
the same ground terminal.
Figure 3
Figure 3 Installing the Option Card
3.
Prepare RJ45 network cable connectors.
In the drives CIMR-A
2A0004 to 0040 and 4A0002 to 0023 the network cable must be routed to the outside through the drive top cover. Use
a pair of diagonal cutters to cut out the perforated openings at the left side of the top cover. Make sure no sharp edges that can damage the
cable remain.
Drives 2A0056 and above, and 4A0031 and above have enough space to keep all wiring inside the unit.
Figure 4
Figure 4 Wiring Routing
4.
Plug in the RJ45 network cable connector into the option.
The network can be established in star, tree, line or ring architecture.
5.
Reinstall the front cover back onto the drive as it was before.
Note: 1.
Take care when wiring the option card so that the front cover easily fits back onto the drive.
2.
Install Cable Cover option to maintain the drive Enclosure Type integrity.
6.
Attach the LED label (10) packaged with the option as shown in
7.
Switch on the drive power supply.
An “AEr” Alarm message indicating that the node address is set to 0 will appear on the drive display.
Set the node address in parameter F6-72.
8.
Cycle the power supply to activate the changed settings. Installation complete.
1 – Connector CN5-C
7 – Ground wire
2 – Connector CN5-B
8 – Use with cutters to create an
opening for cable lines
3 – Connector CN5-A
9 – Operator
4 – Drive grounding terminal (FE)
10 – LED label
5 – Insert connector CN5 here
11 – Front cover
6 – Option card
1 – Opening for network cables
(CIMR-A
2A0004 to 0040, 4A0002 to 0023)
2 – Space for wiring
(CIMR-A
2A0056 to 0211, 4A0031 to 0165)
RUN
ERR
L/A IN
L/A OUT
RUN
ERR
L/A IN
L/A OUT
L/A 1
S/E
L/A 2
MS
7
1
5
6
9
10
2
3
4
8
11
2
1