8 Object Dictionary
24
YASKAWA EUROPE GMBH
YEU SIEP C710616 86A - AC Drive A1000 Option Powerlink - Technical Manual
2040 (Hex) - MEMOBUS/Modbus Read Request
This object can be used to read out the content of drive MEMOBUS/Modbus registers. The address of the MEMOBUS/Modbus must be written in
byte 3 and 4 of Subindex 1, bytes 1 and 2 have to be set to 0. After sending a MEMOBUS/Modbus Read Request to the drive, the MEMOBUS/
Modbus register content can be read out from object 2140H.
For more details on MEMOBUS/Modbus address and data, refer to the MEMOBUS/Modbus/Modbus Data Table in Appendix C of the technical
manual for the drive.
2050 (Hex) - MEMOBUS/Modbus Write Request
Using this object, drive MEMOBUS/Modbus registers can be written. The data must be written in byte 1 and 2 of Subindex 1, the MEMOBUS/
Modbus address must be written in bytes 3 and 4. After sending a MEMOBUS/Modbus Write Request to the drive, the response can be read from
object 2150H.
For more details on MEMOBUS/Modbus address and data, refer to the MEMOBUS/Modbus Data Table in Appendix C of the technical manual for the drive.
2060 (Hex) - MEMOBUS/Modbus Unlimited ENTER Command
Depending on the drive parameter H5-11 setting, an ENTER command must be used to activate drive parameters changed via MEMOBUS/Modbus
Write Commands. The Unlimited ENTER command activates parameters in the drive RAM only. If the drive power is cycled, parameter changes
are lost. If more than one parameter has been changed, it is enough to send only one ENTER command after the last parameter change. Doing so
will activate all changed parameters. This ENTER command can be used without limitations.
To execute this type of ENTER command, “save” (73H + 61H + 76H + 65H) has to be written in object 2060H, subindex 0.
2070 (Hex) - MEMOBUS/Modbus Limited ENTER Command
Depending on the drive parameter H5-11 setting, an ENTER command must be used to activate drive parameters changed via MEMOBUS/Modbus
Write Commands. The limited ENTER command activates parameters in the drive’s RAM and saves them to the EEPROM. When power supply
loss occurs or the power supply is cycled, the drive will operate using the saved parameters. If more than one parameter has been changed, it is
sufficient to send only one ENTER command after the last parameter change. Doing so will activate all changed parameters. This type of ENTER
command can be applied approximately 100,000 times and should be used only when necessary.
To execute this type of ENTER command, “save” (73H + 61H + 76H + 65H) has to be written in object 2070H, subindex 0.
Note: Write access to this object is only allowed in the Powerlink
pre-operational state.
2080 to 3100 (Hex) - Freely Configurable Input Objects
The content of these objects can be freely selected by linking them to drive MEMOBUS/Modbus registers. Refer to
for details.
Index (Hex)
Subindex
Content
Access
PDO Mapping
Data Length
2040
0
Number of entries
Read Only
Possible
1 byte
1
MEMOBUS/Modbus read request
Read/Write
2 + 2 byte
MEMOBUS/Modbus
0000H + Address
Index (Hex.)
Subindex
Content
Access
PDO Mapping
Data Length
2050
0
Number of entries
Read Only
Possible
1 byte
1
MEMOBUS/Modbus Write request
Read/Write
2 + 2 byte
MEMOBUS/Modbus
Data + Address
Index (Hex)
Subindex
Content
Access
PDO Mapping
Data Length
2060
-
Unlimited ENTER command
Read/Write
Possible
4 byte
Index (Hex)
Subindex
Content
Access
PDO Mapping
Data Length
2070
-
Limited enter command
Read/Write
Possible
4 byte
Index (Hex)
<1> Read/Write access when SI-EL3/V is in the Pre-Operational state, Read only access if the SI-EL3/V is in the Operational state or if the drive is running.
Subindex
Content
Default
Access
PDO Mapping
Value
Data Length
2080
0
Number of entries
2
Read Only
No
1 Byte
1
Value of mapped MEMOBUS register.
AAAA = MEMOBUS register 1 value
BBBB = MEMOBUS register 2 value
-
Read/Write
Possible
0xAAAABBBB
4 byte
2
MEMOBUS/Modbus register address of
content 1 and 2
AAAA = MEMOBUS register 1 address
BBBB = MEMOBUS register 2 address
Reg. value=0xFFFF ' Mapping disabled.
Note: Those values can only be changed in Powerlink
pre-operational state. Refer to
for the state
relations.
FFFF (Hex)/FFFF (Hex) Read/Write
No
0xAAAABBBB
4 Byte
2090 to 20C0,
3000, and 3100
0
Number of entries
2
Read Only
No
1 Byte
1
Value of mapped MEMOBUS register.
AAAA = MEMOBUS register value
-
Read/Write
Possible
0xAAAA
2 Byte
2
MEMOBUS/Modbus register address of content
AAAA = MEMOBUS register address.
Note: Those values can only be changed in Powerlink
pre-operational state. Refer to
for the state
relations.
FFFF (Hex)
Read/Write
No
0xAAAA
2 Byte