3.5 Wiring MECHATROLINK-
II
Communications
3-27
3
Wirin
g and Con
nection
3.5
Wiring MECHATROLINK-
II
Communications
The following diagram shows an example of connections between a host controller and a SERVOPACK using
MECHATROLINK-II communications cables (CN6A, CN6B).
Note 1. The length of the cable between stations (L1, L2 ... Ln) must be 0.5 m or more.
2. The total cable length must be L1 + L2 ... + Ln
≤
50.
3. When multiple SERVOPACKs are connected by MECHATROLINK-II communications cable, a terminator must
be installed at the final SERVOPACK.
Ln
L1
L2
Terminator
DC24V