10 Appendix
10-16
Pn50A
2
Input Signal Selection 1
0000 to FFF1
−
1881
After restart
Setup
−
(cont’d)
Parameter
No.
Size
Name
Setting
Range
Units
Factory
Setting
When
Enabled
Classification Reference
Section
Reserved (Do not change.)
Reserved (Do not change.)
Reserved (Do not change.)
P-OT Signal Mapping
Reference
Section
0
Forward run allowed when CN1-13 input signal is ON (closed).
4.3.2
1
Forward run allowed when CN1-7 input signal is ON (closed).
2
Forward run allowed when CN1-8 input signal is ON (closed).
3
Forward run allowed when CN1-9 input signal is ON (closed).
4
Forward run allowed when CN1-10 input signal is ON (closed).
5
Forward run allowed when CN1-11 input signal is ON (closed).
6
Forward run allowed when CN1-12 input signal is ON (closed).
7
Forward run prohibited.
8
Forward run allowed.
9
Forward run allowed when CN1-13 input signal is OFF (open).
A
Forward run allowed when CN1-7 input signal is OFF (open).
B
Forward run allowed when CN1-8 input signal is OFF (open).
C
Forward run allowed when CN1-9 input signal is OFF (open).
D
Forward run allowed when CN1-10 input signal is OFF (open).
E
Forward run allowed when CN1-11 input signal is OFF (open).
F
Forward run allowed when CN1-12 input signal is OFF (open).
4th 3rd 2nd 1st
digit digit digit digit
n.