NOTE 3:
When the altitude is higher than 9843ft (3000m), the
power of the inverter
will start derating, as shown in Figure 7.3:
Pin/Pn
3000 4000
Altitude(m)
100%
70%
-30%/km
Figure 7.4 - PVI 50/60TL Derating Curve with High Altitude
NOTE 4:
The inverter can output the AC power with full loads within 100%~110% of
the rated grid voltage. When the grid voltage is lower than rated voltage, the output
current will be limited within the allowable maximum current.
20%
40%
60%
80%
100%
Po/Pn
Un 1.1*Un
Grid Voltage (Vac)
Figure 7.5 - PVI 50/60TL Derating Curve of Grid Voltage
Po/Pn
480
528