PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E
Page 41 of 102
No.
Tools
Where used
1.
#3 Phillips screwdriver
Remove cover, external grounding
2.
1/4” flat head bit
Internal grounding bar
3.
14mm hex socket wrench
AC terminal block
4.
Torque wrench
AC terminal block
5.
Diagonal pliers
Cut cables
6.
Wire stripping pliers
Remove insulation of wires
7.
Crimping pliers
Crimp terminal
Table 2.11 - Torque Values
AC output terminal block
132 in-lbs (15 N.m.)
Internal grounding bar
50 in-lbs (4 N.m.)
Internal grounding stud
50 in-lbs (4 N.m.)
External grounding point
50 in-lbs (4 N.m.)
Figure 2.34 - AC cables’ crimp lug specification (a) Standard (b) Metric