PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E
Page 49 of 102
Table 2.15 – Overview of Ethernet Card
Item
Configuration Description and Function
Ethernet Port
For connecting to the internet
USB Port
Firmware upgrade via USB drive
External RS485
1.RS485+
2. RS485-
3 .Ground
For RS485 communication with other inverters
Internal RS485
For RS485 communication with the inverter
communication board
S3 Switch
Selector switch for setting the 120Ω terminal
resistor of the third party data logger RS485
communication.
S4 Switch
Selector switch for setting the 120Ω terminal
resistor of the RS485 communication between
the inverters.
Reset Switch
When pressed for over 5sec, the inverter’s
Ethernet Network Card will be restored to the
factory setting.
2.4.3 Modbus Connections for Third Party Monitoring Systems
The PVI 50/60TL inverters can be connected to an external Data Acquisition System
(DAS) via an RS485 shielded twisted pair serial connection as shown in Figure 2.42.
These inverters can communicate with an external monitoring system via the
standard Modbus RTU protocol.
Figure 2-42 - PVI 50/60TL Inverters in a RS-485 Daisy Chain Connection to an
External DAS