9.0: Accessory Options
The PVI 50/60TL has several orderable options that allow the inverter to support a
wide range of real life applications.
9.1
Fuse Bypass
OPT-FUSEBYPASS-PVI-50-60TL
allows customers to combine the DC inputs outside of
the inverter and enter with only one or two combined inputs. Torque the provided
hardware to 16 in-lbs (1.8 N.m). Note that the negative inputs are combined already.
The unit is separated on the positive input.
Figure 8.1 – Fuse Bypass Three Inputs (Three Independent MPPTs)
Bypass Input Terminal Instructions:
1.
Remove the protection cover.
2.
Use a No. 2 Phillips head screwdriver to install the bypass input terminals, 3 sets,
torque value of 14 in-lbs (1.6 N.m.).
3.
Use a No. 10 wrench to screw DC input cable on the bypass input terminals, torque
value of 50 in-lbs (6.0 N.m.).
4.
Reinstall the protection cover.