Table 4.3 Protection Parameters (IEEE1547)
REMARK:
Please contact Applications Engineering if you need to change any of the
voltage settings.
Grid Over Voltage Protection
Parameter name
Description
Setup range (lower limit,
default & upper limit)
GridVoltMax1
Threshold value of Level 1 Max.
grid voltage
{100.00%, 110.00%,
150.00%}
VoltMaxTripTime1(s)
Threshold value of Level 1 Max.
grid trip voltage
{0, 1.00, 655}
GridVoltMax2
Threshold value of Level 2 Max.
grid voltage
{100.00%, 120.00%,
135.00%}
VoltMaxTripTime2(s)
Threshold value of Level 2 Max.
grid trip voltage
{0, 0.16, 655}
GridVoltMax3
Threshold value of Level 3 Max.
grid voltage
{100.00%, 120.00%,
135.00%}
VoltMaxTripTime3(s)
Threshold value of Level 3 Max.
grid trip voltage
{0, 0.16, 655}
Grid Low Voltage Protection
Parameter name
Description
Setup range (lower limit,
default & upper limit)
GridVoltMin1
Threshold value of Level 1 Min.
grid voltage
{30.00%, 88.00%,
100.00%}
VoltMinTripTime1(s)
Threshold value of Level 1 Min.
grid trip voltage
{0, 2.0, 655.36}
GridVoltMin2
Threshold value of Level 2 Min.
grid voltage
{30.00%, 60.00%,
100.00%}
VoltMinTripTime2(s)
Threshold value of Level 2 Min.
grid trip voltage
{0, 0.16, 655}
GridVoltMin 3
Threshold value of Level 3 Min.
grid voltage
{30.00%, 45.00%,
100.00%}
VoltMinTripTime3(s)
Threshold value of Level 3 Min.
grid trip voltage
{0, 1.2, 655}
Grid Low Frequency Protection
Parameter name
Description
Setup range (lower limit,
default & upper limit)
GridFrqMin1
Protection threshold value of
Level 1 Min. grid frequency
{54, 59.5, 60}
FrqMinTripT1(s)
Trip time of Level 1 Min. grid
frequency
{0, 2, 655 }