No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
F6-26
(03CA)
MECHATROLINK
bUS Errors Detected
Num of SI-T BUS
Sets the number of option communication errors (bUS).
Default: 2
Min.: 2
Max.: 10
–
F6-30
(03CB)
PROFIBUS-DP Node
Address
PB Node Address
Sets the node address.
Default: 0
Min.: 0
Max.: 125
–
F6-31
(03CC)
PROFIBUS-DP Clear
Mode Selection
PB Clear Select
0: Reset to Zero
1: Hold Prev Value
0: Resets drive operation with a Clear mode command.
1: Maintains the previous operation state when Clear mode
command is given.
Default: 0
Range: 0, 1
–
F6-32
(03CD)
PROFIBUS-DP Data
Format Selection
PB Map Select
0: PPO Type
1: Conventional
0: PPO Type
1: Conventional
Default: 0
Range: 0, 1
–
F6-45
(02FB) BACnet Node Address BAC Node Address
Sets the node address.
Default: 1
Min.: 0
Max.: 127
–
F6-46
(02FC) BACnet Baud Rate
BAC Baud Rate
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19.2 kbps
5: 38.4 kbps
6: 57.6 kbps
7: 76.8 kbps
8: 115.2 kbps
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19.2 kbps
5: 38.4 kbps
6: 57.6 kbps
7: 76.8 kbps
8: 115.2 kbps
Default: 3
Range: 0 to 8
–
F6-47
(02FD) Rx to Tx Wait Time
Rx to Tx Wait T
Rx to Tx Wait Time
Default: 5 ms
Min.: 5
Max.: 65
–
F6-48
(02FE)
BACnet Device Objcet
ID 0
BAC Dev Obj Id 0
BACnet device object ID
Default: 0
Min.: 0
Max.: FFFF
–
F6-49
(02FF)
BACnet Device Objcet
ID 1
BAC Dev Obj Id 1
BACnet device object ID
Default: 0
Min.: 0
Max.: 3F
–
F6-50
(03C1)
DeviceNet MAC
Address
DN MAC Address
Selects the drive MAC address.
Default: 64
Min.: 0
Max.: 64
–
F6-51
(03C2)
DeviceNet
Communication Speed
DN Baud Rate
0: 125 kbps
1: 250 kbps
2: 500 kbps
3: Set from Network
4: Auto Detect
0: 125 kbps
1: 250 kbps
2: 500 kbps
3: Adjustable from network
4: Detect automatically
Default: 4
Range: 0 to 4
–
F6-52
(03C3) DeviceNet PCA Setting PCA Selection
Sets the format of the data set from the DeviceNet master to the
drive.
Default: 21
Min.: 0
Max.: 255
–
F6-53
(03C4) DeviceNet PPA Setting PPA Selection
Sets the format of the data set from the drive to the DeviceNet
master.
Default: 71
Min.: 0
Max.: 255
–
F6-54
(03C5)
DeviceNet Idle Mode
Fault Detection
DN Idle Flt Det
0: Stop
1: Ignore
0: Enabled
1: Disabled, no fault detection
Default: 0
Range: 0, 1
–
F6-55
(03C6)
DeviceNet Baud Rate
Monitor
DN BAUD RATE
MEM
0: 125 kbps
1: 250 kbps
2: 500 kbps
Verifies the baud rate running on the network.
0: 125 kbps
1: 250 kbps
2: 500 kbps
Default: 0
Range: 0 to 2
–
F6-56
(03D7)
DeviceNet Speed
Scaling
Speed Scale
Sets the scaling factor for the speed monitor in DeviceNet.
Default: 0
Min.: -15
Max.: 15
–
F6-57
(03D8)
DeviceNet Current
Scaling
Current Scale
Sets the scaling factor for the output current monitor in
DeviceNet.
Default: 0
Min.: -15
Max.: 15
–
B.7 F: Options
370
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Содержание iQpump1000
Страница 2: ......
Страница 12: ...This Page Intentionally Blank 12 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 308: ...6 3 Drive Replacement This Page Intentionally Blank 308 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 448: ...B 16 U Monitors This Page Intentionally Blank 448 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 486: ...C 12 Self Diagnostics This Page Intentionally Blank 486 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 507: ......