C.4 MEMOBUS/Modbus Setup Parameters
u
MEMOBUS/Modbus Serial Communication
Changes to MEMOBUS/Modbus communications settings become effective after restarting the drive.
n
H5-01: Drive Node Address
Sets the drive station node number (address) for MEMOBUS/Modbus terminals R+, R-, S+, S- . .
Note:
Cycle the power after changing this parameter to enable the new setting.
No.
Name
Setting Range
Default
H5-01
Drive Slave Address
0 to FF
1F (Hex)
Each slave drive must be assigned a unique slave address for serial communications to work. Setting H5-01 to any value
besides 0 assigns the drive its address in the network. Slave addresses do not need to be assigned in sequential order, but no
two drives may share the same address.
n
H5-02: Communication Speed Selection
Sets the MEMOBUS/Modbus communications speed.
Note:
Cycle the power after changing this parameter to enable the new setting.
No.
Name
Setting Range
Default
H5-02
Communication Speed Selection
0 to 8
3
H5-02
Communication Speed
H5-02
Communication Speed
0
1200 bps
5
38400 bps
1
2400 bps
6
57600 bps
2
4800 bps
7
76800 bps
3
9600 bps
8
115200 bps
4
19200 bps
n
H5-03: Communication Parity Selection
Sets the parity used for communications.
Note:
Cycle power for the setting to take effect.
No.
Name
Setting Range
Default
H5-03
Communication Parity Selection
0 to 2
0
Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity
n
H5-04: Stopping Method after Communication Error
Selects the stopping method after a communications error (CE) has occurred.
No.
Name
Setting Range
Default
H5-04
Stopping Method after CE
0 to 4
3
Setting 0: Ramp to stop (uses the deceleration time currently enabled)
Setting 1: Cost to stop
Setting 2: Fast Stop
Setting 3: Alarm only (continue operation)
Setting 4: Run at H5-14
Note:
1.
This setting is available in drive software versions PRG: 8552 and later.
2.
This setting is not available in drive models 4A0930 and 4A1200.
This setting will trigger a “CE – Comm Loss” alarm and cause the drive to run at the speed set in H5-14 speed when a
Communication Error (CE) occurs.
C.4 MEMOBUS/Modbus Setup Parameters
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
455
C
MEMOBUS/Modbus Communications
Содержание iQpump1000
Страница 2: ......
Страница 12: ...This Page Intentionally Blank 12 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 308: ...6 3 Drive Replacement This Page Intentionally Blank 308 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 448: ...B 16 U Monitors This Page Intentionally Blank 448 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 486: ...C 12 Self Diagnostics This Page Intentionally Blank 486 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 507: ......