13.
The pump can be run in HAND (LOCAL) Mode for maintenance purposes by pressing the HAND key while the drive
is stopped. The HAND key acts as a start button. Press the OFF button to stop the drive. Press AUTO to return the
drive to geothermal control. The HAND speed reference can be set in P5-02 (Hand Reference 1). Disable the HAND
key by setting P5-04 to 0 (disabled).
n
Related Parameters, Faults, and Alarms
No.
Parameter Name
Setting Values
A1-01
Access Level Selection
Default: 2
Range: 0 to 3
A1-03
Initialize Parameters
Default: 0
Range: 0 to 5550; 6008 to 6014; 7770, 7771
b1-02
Run Command Selection 1
Default: 0
Range: 0 to 3; 6 to 8
E2-01
Motor Rated Current
Default:
Min.: 10% of drive rated current
Max.: 200% of drive rated current
E2-04
Number of Motor Poles
Default: 2
Min.: 2
Max.: 48
P1-03
Feedback Device Scaling
Default: 145.0 PSI
Min.: 0.1
Max.: 6000.0
P1-04
Start / Draw Down Level
Default: 0.0
Min.: -999.9
Max.: 999.9
P1-06
Minimum Pump Speed
Default: 40.0 Hz
Min.: 0.0
Max.: [E1-04]
P1-11
High Feedback Level
Default: 0.0 PSI
Min.: 0.0
Max.: 6000.0
P2-02
Sleep Level
Default: 0.0 Hz
Min.: 0.0
Max.: 6000.0
P4-10
AUTO Mode Operator Run Power Down Storage
Default: 0
Range: 0, 1
P5-02
HAND Speed Reference 1
Default: 40.0 Hz
Min.: 0
Max.: [E1-04]
P5-04
HAND Key Function Selection
Default: 1
Range: 0, 1
Q1-01
PID Controller Setpoint 1
Default: 0.0
Min.: 0.0
Max.: 6000.0
Q2-01
Minimum Geothermal Temperature Input
Default: 0.0
°
F
Min.: -110.0
Max.: 275.0
Q2-02
Maximum Geothermal Temperature Input
Default: 120.0
°
F
Min.: -100.0
Max.: 275.0
Q2-03
Minimum Geothermal Speed
Default: 40.0 Hz
Min.: 0.0
Max.: 400.0
Q2-04
Maximum Geothermal Speed
Default: 60.0 Hz
Min.: 0.0
Max.: 400.0
4.6 iQpump Presets and Functions
156
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Содержание iQpump1000
Страница 2: ......
Страница 12: ...This Page Intentionally Blank 12 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 308: ...6 3 Drive Replacement This Page Intentionally Blank 308 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 448: ...B 16 U Monitors This Page Intentionally Blank 448 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 486: ...C 12 Self Diagnostics This Page Intentionally Blank 486 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 507: ......