n
Vertical Suspension of Drive Models 2A0360, 2A0415, and 4A0250 to 4A1200
Models 2A0360, 2A0415, and 4A0250 to 4A0675
When vertical suspension of the drive is required in an enclosure panel, change the orientation of the eye bolts for these models
by turning the eye bolts counterclockwise 90 degrees.
Figure 2.6 Adjusting Angle of Eye Bolts
Models 4A0930 and 4A1200
When suspending models 4A0930 or 4A1200 with wires, follow the procedure described below.
WARNING! Crush Hazard. Use an adequate length of wire to ensure a 50° or wider suspension angle as illustrated in
maximum allowable load of the eye bolts cannot be guaranteed when the drive is suspended with the wires at angles less than 50°. Failure
to comply may result in serious injury or death from falling equipment.
1.
Remove the four eye bolts from the drive side panels and fix them securely on the top panel.
Eye bolt
Figure 2.7 Eye Bolt Repositioning
2.
Pass wire through the holes of all four eye bolts.
A
B
C
A – Eye bolt
B – Wires
C – Suspending angle: 50° or greater
Figure 2.8 Suspension Wire Angle Example
2.1 Mechanical Installation
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
39
2
Mechanical Installation
Содержание iQpump1000
Страница 2: ......
Страница 12: ...This Page Intentionally Blank 12 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 308: ...6 3 Drive Replacement This Page Intentionally Blank 308 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 448: ...B 16 U Monitors This Page Intentionally Blank 448 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 486: ...C 12 Self Diagnostics This Page Intentionally Blank 486 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 507: ......