Network State
Display
Drive is in Auto Mode, Lag operation and is
holding the speed at the time it made the
switch from being a lead drive to a lag. Speed
is held until P9-07 time expires. The Home
screen will display U1-01 instead of U5-99.
Lag: Fixed Hold
- MODE -
DRV RDY
Home
U1-02=
U1-91=
59.41Hz
99.8PSI
U1-01= 59.41
HZ
Drive is in Auto Mode, Lag operation and is
running at the speed set in P9-06. The Home
Screen will display U1-01 instead of U5-99.
Lag: Fixed P9-06
- MODE -
DRV RDY
Home
U1-02=
U1-91=
55.00Hz
99.9PSI
U1-01= 55.00
HZ
Drive is in AUTO Mode, Lag operation and
is following the speed of the current Lead
drive. The Home screen will display U1-01
instead of U5-99.
Lag: Follow Lead
- MODE -
DRV RDY
Home
U1-02=
U1-91=
51.35Hz
98.9PSI
U1-01= 51.37
HZ
Drive is in AUTO Mode, Lead operation with
Geothermal Enabled. The Home screen will
display U1-01 instead of U5-99
Lead: Geothermal
- MODE -
DRV RDY
Home
U1-02=
U1-80=
44.82Hz
83.6˚F
U1-01= 48.00
HZ
n
PI Feedback via Network
The Network PI Feedback comes from a drive on the network with a valid analog PI feedback source and can be used as the
primary or secondary feedback source for a networked drive.
Set P9-02 to 0 if a drive has an analog PI feedback device installed and switching to network as a backup is not desired.
if a drive has an analog PI feedback device installed and the network PI feedback is considered as a backup, set P9-02 to 1 for
no alarm message when switched and set P9-02 to 2 for an alarm.
Set P9-02 to 3 if a drive has no analog PI feedback device installed and relies solely on the analog PI feedback of another
networked drive.
Note:
Connect an analog PI feedback device to each drive for best performance.
n
Related Parameters
No.
Parameter Name
Setting Values
H5-01
Drive Node Address
Default: 1F (Hex)
Min.: 0
Max.: FF
P1-01
Pump Mode
Default: 0
Range: 0, 1, 3
P9-02
Feedback Source
Default: 0
Range: 0 to 3
4.6 iQpump Presets and Functions
182
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Содержание iQpump1000
Страница 2: ......
Страница 12: ...This Page Intentionally Blank 12 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 308: ...6 3 Drive Replacement This Page Intentionally Blank 308 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 448: ...B 16 U Monitors This Page Intentionally Blank 448 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 486: ...C 12 Self Diagnostics This Page Intentionally Blank 486 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 507: ......