Drive Model
Terminal
Recomm.
Gauge Without
Additional
Impedance
AWG, kcmil
Recomm.
Gauge With
Additional
AWG, kcmil
Wire Range
Screw
Size
Tightening Torque
N·m (lb.in.)
4
o
0296
R/L1, S/L2
3/0
1 X 2P
up to 250 kcmil
M12
32 to 40 (283 to 354)
U/T1, V/T2, W/T3
3
2
upto 250 kcmil
⊖
,
⊕
1
-
-
up to 250 kcmil
⊕
3
-
-
up to 250 kcmil
M10
18 to 23 (159 to 204)
GND
1
2/0
up to 250 kcmil
M12
32 to 40 (283 to 354)
4
o
0362
R/L1, S/L2
1 X 2P
2/0 X 2P
up to 250 kcmil
M12
32 to 40 (283 to 354)
U/T1, V/T2, W/T3
1
1/0
up to 250 kcmil
⊖
,
⊕
1
-
-
up to 250 kcmil
⊕
3
-
-
up to 250 kcmil
M10
18 to 23 (159 to 204)
GND
2/0
3/0
up to 250 kcmil
M12
32 to 40 (283 to 354)
4
o
0414
R/L1, S/L2
3/0 X 2P
3/0 X 2P
up to 250 kcmil
M12
32 to 40 (283 to 354)
U/T1, V/T2, W/T3
3/0
3/0
up to 250 kcmil
⊖
,
⊕
1
-
-
up to 250 kcmil
⊕
3
-
-
up to 250 kcmil
GND
1/0 X 2P
1/0 X 2P
up to 250 kcmil
4
o
0515
R/L1, S/L2
4/0 X 2P
3/0 X 2P
up to 250 kcmil
M12
32 to 40 (283 to 354)
U/T1, V/T2, W/T3
3/0
3/0
up to 250 kcmil
⊖
,
⊕
1
-
-
up to 250 kcmil
⊕
3
-
-
up to 250 kcmil
GND
1/0 X 2P
1/0 X 2P
up to 250 kcmil
4
o
0675
R/L1, S/L2
1 X 4P
1 X 4P
up to 250 kcmil
M12
32 to 40 (283 to 354)
U/T1, V/T2, W/T3
4/0
4/0
up to 250 kcmil
⊖
,
⊕
1
-
-
up to 250 kcmil
⊕
3
-
-
up to 250 kcmil
GND
3/0 X 2P
3/0 X 2P
up to 250 kcmil
<1> Refer to local codes while selecting wire size for terminals
2 if these terminals need to be used for other optional power devices.
<2> The wire size recommended for terminal
2 is for DC type additional impedance only. See the additional impedance type recommended
before choosing wire size for terminals
Table A.18 600 V Single-Phase Main Circuit Wiring and Tightening Torques
Drive Model
Terminal
Recomm.
Gauge Without
Additional
Impedance
AWG, kcmil
Recomm.
Gauge With
Additional
Impedance
AWG, kcmil
Wire Range
Screw
Size
Tightening Torque
N·m (lb.in.)
5
o
0003
5
o
0004
5
o
0006
5
o
0009
R/L1, S/L2
14
14
14 to 10
M4
1.2 to 1.5 (10.6 to 13.3)
U/T1, V/T2, W/T3
14
14
14 to 10
⊖
,
⊕
1,
⊕
2
-
14
14 to 10
B1, B2
-
-
14 to 10
GND
14
14
14 to 10
5
o
0011
R/L1, S/L2
12
12
12 to 6
M4
2.1 to 2.3 (18.6 to 20.4)
U/T1, V/T2, W/T3
12
12
12 to 6
⊖
,
⊕
1,
⊕
2
-
12
12 to 6
B1, B2
-
-
12 to 10
GND
12
12
12 to 10
M5
2.0 to 2.5 (17.7 to 22.1)
A.4 Drive Derating Data
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
335
A
Specifications
Содержание iQpump1000
Страница 2: ......
Страница 12: ...This Page Intentionally Blank 12 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 308: ...6 3 Drive Replacement This Page Intentionally Blank 308 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 448: ...B 16 U Monitors This Page Intentionally Blank 448 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 486: ...C 12 Self Diagnostics This Page Intentionally Blank 486 YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive iQpump1000 User Manual...
Страница 507: ......