Broadcast Messages
Data can be written from the master to all slave devices at the same time.
The slave address in a broadcast command message must be set to 00H. All slaves will receive the message, but will not
respond.
u
Fault Trace Contents
The table below shows the fault codes that can be read out by MEMOBUS/Modbus commands from the U2-
and
U3-
monitor parameters.
Table C.5 Fault Trace / History Register Contents
Register No.
Contents
0001H
Digital Input Command
bit 0
Forward Run (0: Stop 1: Run)
bit 1
Direction Command (0: Forward, 1: Reverse)
bit 2, 3
Reserved
bit 4
External Fault
bit 5
Fault Reset
bit 6 to B
Reserved
bit C
Multi-Function Contact Input 5
bit D
Multi-Function Contact Input 6
bit E
Multi-Function Contact Input 7
bit F
Multi-Function Contact Input 8
0002H
Frequency Reference
30000/100%
Fault Code
Fault Name
Fault Code
Fault Name
0001H
Fuse Blowout (CFA FU)
0098H
PWM Feedback Fault (CPF23)
0002H
Undervoltage (Uv1)
0099H
Drive Unit Signal Fault (CPF24)
0003H
Undervoltage (CFA CUV)
009BH
ASIC BB Circuit Error (CPF26)
0004H
In-rush Prevention Circuit Error (Uv3)
009CH
ASIC PWM Setting Register Error (CPF27)
0005H
IGBT Fault (CFA IGBT_FLT)
009DH
ASIC PWM Pattern Error (CPF28)
0006H
Ground Fault (GF)
009EH
ASIC On-Delay Error (CPF29)
0007H
Overcurrent (CFA OC)
00A0H
ASIC Code Error (CPF31)
0008H
Overvoltage 1 (CFA OV)
00A1H
ASIC Start-p Error (CPF32)
0009H
IGBT Overheating (CFA OH)
00A2H
Watch-dog Error (CPF33)
000AH
IGBT Overheating 1 (CFA OH1)
00A3H
ASIC Power/Clock Error (CPF34)
000BH
Motor Overload (oL1)
00A9H
Control Circuit Error (CPF40)
000CH
Drive Overload (oL2)
00AAH
Control Circuit Error (CPF41)
000DH
Overtorque Detection 1 (oL3)
00ABH
Control Circuit Error (CPF42)
000EH
Overtorque Detection 2 (oL4)
00ACH
Control Circuit Error (CPF43)
0011H
External Fault at contact input terminal 3 (EF3)
0101H
Option compatibility error (oFA00)
0012H
External Fault at contact input terminal 4 (EF4)
0102H
Option not properly connected (oFA01)
0013H
External Fault at contact input terminal 5 (EF5)
0103H
Same type of option card already connected (oFA02)
0014H
External Fault at contact input terminal 6 (EF6)
0106H
A/D Conversion Error (oFA05)
0015H
External Fault at contact input terminal 7 (EF7)
0107H
Option Response Error (oFA06)
0016H
External Fault at contact input terminal 8 (EF8)
0111H
Option RAM Fault (oFA10)
0017H
Fan Fault (FAn)
0112H
Option Operation Mode Fault (SLMOD) (oFA11)
0018H
Overspeed (oS)
0113H
Drive Receive CRC Error (oFA12)
0019H
Speed Deviation (dEv)
0114H
Drive Receive Frame Error (oFA13)
001AH
PG Disconnect (PGo)
0115H
Drive Receive Abort Error (oFA14)
001CH
Output Phase Loss (LF)
0116H
Option Receive CRC Error (oFA15)
001EH
External Digital Operator Connection Fault (oPr)
0117H
Option Receive Frame Error (oFA16)
001FH
EEPROM Write Error (Err)
0118H
Option Receive Abort Error (oFA17)
0021H
MEMOBUS/Modbus Communication Error (CE)
0131H
Comm. ID Error (oFA30)
0022H
Option Communication Error (bUS)
0132H
Model Code Error (oFA31)
Содержание FSDrive-MV1000 Series
Страница 8: ...8 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 38: ...1 4 Component Names and Configurations 38 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 106: ...3 9 Wiring Check 106 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 136: ...4 9 Checking and Saving Parameter Default Values 136 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 210: ...6 7 Spare Parts 210 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 222: ...B 1 European Standards 222 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...