2.2 Mechanical Installation
YASKAWA ELECTRIC
TOEP C710687 02B FSDrive-MV1000 Instructions
51
Mech
ani
c
al
In
st
al
la
ti
on
2
Table 2.10 Transportation Procedure 2 (Class: 4 kV)
DANGER!
Do not remove bolts from the top of the transformer panel and fit hoisting tackle to lift it. Failure to comply could result in
deformation or falling of the transformer panel.
DANGER!
When lifting the transformer panel, take care to ensure that the housing is not damaged by contact with the ceiling plate
or other parts. Failure to comply could result in deformation of the transformer panel or damage to the ceiling plate.
Transportation Procedure
1. Insert wire ropes for lifting through the support hook installation openings on the top of the drive.
Note:
Drives are shipped with the support hook installation openings fitted.
Figure 2.11
Figure 2.11 Inserting Wire Ropes for Lifting
2. Attach the wire ropes for lifting to the support hooks on the transformer to lift the transformer panel.
Figure 2.12
Figure 2.12 Suspension of Transformer Panel
3. Ensure that the hanging angle is 45
°±
15
°
.
Support hook
installation opening
Front view
Top view
Wire ropes for lifting
Drive
Transformer
support hooks
Wire ropes for lifting
Front view
Hanging angle of 45
°
±15
°
Содержание FSDrive-MV1000 Series
Страница 8: ...8 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 38: ...1 4 Component Names and Configurations 38 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 106: ...3 9 Wiring Check 106 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 136: ...4 9 Checking and Saving Parameter Default Values 136 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 210: ...6 7 Spare Parts 210 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 222: ...B 1 European Standards 222 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...