5.6 Operator Programming Error
5.6 Operator Programming Error
u
oPE Codes, Causes, and Possible Solutions
An Operator Programming Error (oPE) occurs when a contradictory parameter is set or an individual parameter is set to
an inappropriate value.
The drive will not operate until the parameter or parameters causing the problem are set correctly. An oPE, however, does
not trigger a contact terminal set for fault or alarm output. If an oPE occurs, investigate the cause and refer to
for the appropriate action. When an oPE appears on the digital operator display, press the ENTER button to view U1-18
and see which parameter is causing the oPE error.
Table 5.15 oPE Codes, Causes, and Possible Solutions
Digital Operator Display
Error Name
oPE01
Drive Capacity Setting Fault
Drive capacity and the value set to o2-04 do not match.
Cause
Possible Solutions
The drive model selection (o2-04) and the actual capacity
of the drive are not the same.
Correct the value set to o2-04.
Digital Operator Display
Error Name
oPE02
Parameter Range Setting Error
Parameters were set outside the possible setting range.
Cause
Possible Solutions
Parameters were set outside the possible setting range.
Use U1-18 to find parameters set outside the range. Set the parameters to the proper
values.
Motor rated current and the motor no-load current setting
in the drive are incorrect.
• There has been an attempt to set the motor rated current in E2-01 to a value lower
than the no-load current set in E2-03.
• Set the E2-01 value higher than the E2-03 value.
• If E2-01 must be set to a value lower than the default setting of E2-03, first lower the
value assigned to E2-03, then change the setting in E2-01 as necessary.
Note:
When multiple errors occur simultaneously, other errors are given precedence over oPE02.
Digital Operator Display
Error Name
oPE03
Contact Input Selection Error
An incorrect function assignment is set for contact inputs H1-01 to H1-16.
Cause
Possible Solutions
The same function is assigned to more than one contact
input.
Excludes “Not used” and “External Fault.”
• Ensure all contact inputs are assigned to different functions.
• Re-enter the contact settings to ensure there is no duplication.
The Up command was set but the Down command was
not, or vice versa (settings 10 vs. 11).
Correctly set functions that need to be enabled in combination with other functions.
The Up 2 command was set but the Down 2 command was
not, or vice versa (settings 75 vs. 76).
Run/Stop command for a 2-wire sequence was set
(H1-
= 42), but Forward/Reverse command
(H1-
= 43) was not.
Two of the following functions are set simultaneously:
• Up/Down Command (10 vs. 11)
• Up 2/Down 2 Command (75 vs. 76)
• Hold Accel/Decel Stop (A)
• Analog Frequency Reference Sample/Hold (1E)
• Offset Frequency 1, 2, 3 Calculations (44, 45, 46)
• Check if contradictory settings have simultaneously been assigned to the contact
input terminals.
• Correct the contact input settings.
The Up/Down command (10, 11) and PID control (b5-01)
are enabled simultaneously.
Set b5-01 to 0 to disable the Up/Down command.
Содержание FSDrive-MV1000 Series
Страница 8: ...8 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 38: ...1 4 Component Names and Configurations 38 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 106: ...3 9 Wiring Check 106 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 136: ...4 9 Checking and Saving Parameter Default Values 136 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 210: ...6 7 Spare Parts 210 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 222: ...B 1 European Standards 222 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...