4.2 Using the Digital Operator
YASKAWA ELECTRIC
TOEP C710687 02B FSDrive-MV1000 Instructions
109
St
ar
t-
Up Pro
gr
ammi
ng
&
O
p
er
at
io
n
4
4.2 Using the Digital Operator
Use the digital operator to enter Run and Stop commands, edit parameters, and display data including fault and alarm
information.
u
Keys and Displays
Figure 4.1
Figure 4.1 Keys and Displays on the Digital Operator
No.
Key
Name
Function
1
Function Key
(F1, F2)
The functions assigned to F1 and F2 vary depending on the menu that is currently displayed. The
name of each function appears in the lower half of the display window. Refer to
for the details of the functions assigned.
2
<1> The STOP key has highest priority.
Pressing the
will always cause the drive to stop the motor, even if a Run command is active at any external Run command source. To
disable the
key priority, set parameter o2-02 to 0.
<2> The LO/RE key can only switch between LOCAL and REMOTE when the drive is stopped.
To disable the
key to prohibit switching between LOCAL and REMOTE, set parameter o2-01 to 0.
ESC Key
• Returns to the previous display.
• Moves the cursor one space to the left.
• Pressing and holding this button will return to the Frequency Reference display.
3
RESET Key
• Moves the cursor to the right.
• Resets the drive to clear a fault situation.
4
RUN Key
Runs the drive in the LOCAL mode.
5
Up Arrow Key
• Scrolls up to display the next item.
• Selects parameter numbers and increments setting values.
6
Down Arrow Key
• Scrolls down to display the next item.
• Selects parameter numbers and decrements setting values.
7
STOP Key
Stops drive operation.
8
ENTER Key
• Enters parameter values and settings.
• Selects a menu item to move between displays.
9
LO/RE Selection
Key
Switches drive control between the digital operator (LOCAL) and the control circuit terminals
(REMOTE).
10
RUN Light
Lit while the drive is operating the motor. Refer to
ALARM (ALM) LED Displays on page 111
for
details.
11
LO/RE Light
Lit while the digital operator is selected to run the drive (LOCAL mode).
12
ALM Light
Refer to
ALARM (ALM) LED Displays on page 111
for details.
LO
RE
F2
F1
ESC
RUN
STOP
ENTER
RESET
ALM
DIGITAL OPERATOR JVOP-180
1
2
3
4
5
6
7
8
9
10
11
12
F1
F2
RE
LO
RUN
STOP
RE
LO
Содержание FSDrive-MV1000 Series
Страница 8: ...8 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 38: ...1 4 Component Names and Configurations 38 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 106: ...3 9 Wiring Check 106 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 136: ...4 9 Checking and Saving Parameter Default Values 136 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 210: ...6 7 Spare Parts 210 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 222: ...B 1 European Standards 222 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...