6
-104
Note Communications error details are stored until an fault reset is input (you can also reset while the Unit is operating).
002CH
Inverter status
Bit 0
Operation
1: Operating
Bit 1
Zero-speed
1: Zero-speed
Bit 2
Frequency matching
1: Matched
Bit 3
User-defined speed matching
1: Matched
Bit 4
Frequency detection 1
1: Output frequency
≤
L4-01
Bit 5
Frequency detection 2
1: Output frequency
≥
L4-01
Bit 6
Inverter startup completed
1: Startup completed
Bit 7
Low voltage detection 1:
Detected
Bit 8
Baseblock
1: Inverter output baseblock
Bit 9
Frequency reference mode
1: Not communications 0: Communications
Bit A
Run Command mode
1: Not communications 0: Communications
Bit B
Overtorque detection
1: Detected
Bit C
Frequency reference lost
1: Lost
Bit D
Retrying error
1: Retrying
Bit E
Error (including MEMOBUS communications time-out) 1:Error occurred
Bit F
MEMOBUS communications time-out 1: Timed out
002DH
Multi-function contact output status
Bit 0
Multi-function contact output (terminal M1-M2) 1: ON 0: OFF
Bit 1
Multi-function PHC output 1 (terminal P1 - PC) 1: ON 0: OFF
Bit 2
Multi-function PHC output 2 (terminal P2 - PC) 1: ON 0: OFF
Bits 3 to F
Not used
002EH - 0030H Not used
0031H
Main circuit DC voltage
0032H
Torque monitor (Unit: 1/0.1%)
0033H
Output power (U1-08)
0034H - 0037H
Not used
0038H
PID feedback quantity (Input equivalent to 100%/Max. output frequency; 10/1%; without sign)
0039H
PID input quantity (±100%/±Max. output frequency; 10/1%; with sign)
003AH
PID output quantity (±100%/±Max. output frequency; 10/1%; with sign)
003BH
CPU software number
003CH
Flash software number
003DH
Communications error details
Bit 0
CRC error
Bit 1
Invalid data length
Bit 2
Not used
Bit 3
Parity error
Bit 4
Overrun error
Bit 5
Framing error
Bit 6
Time-out
Bits 7 to F
Not used
003EH
kVA setting
003FH
Control method
Register No.
Contents