Multi-function Analog Outputs: H4
User constants for multi-function analog outputs are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
H4-01
Monitor
selection
(terminal
FM)
Sets the number of the moni-
tor item to be output (U1-
) from terminal FM. The
monitor items that can be set
depends on the control
method.
4, 10 to 14, 25, 28 to 31, 34,
35, 39 to 43 cannot be set.
1 to 99
2
No
A
A
A
A
41DH 6-91
H4-02
Gain (termi-
nal FM)
Sets the multi-function ana-
log output 1 voltage level
gain.
Sets whether the monitor
item output will be output in
multiples of 10 V.
The maximum output from
the terminal is 10 V.
A meter calibration function
is available.
*
0.00 to
2.50
1.00
Yes
Q
Q
Q
Q
41EH
4-6
6-91
H4-03
Bias (termi-
nal FM)
Sets the multi-function ana-
log output 1 voltage level
bias.
Sets output characteristic up/
down parallel movement as a
percentage of 10 V.
The maximum output from
the terminal is 10 V.
A meter calibration function
is available.
*
-10.0 to
+10.0
0.0%
Yes
A
A
A
A
41FH 6-91
H4-04
Monitor
selection
(terminal
AM)
Sets the number of the moni-
tor item to be output (U1-
) from terminal AM.
The monitor items that can
be set depends on the control
method.
4, 10 to 14, 25, 28 to 31, 34,
35, 39 to 43 cannot be set.
1 to 99
3
No
A
A
A
A
420H 6-91
H4-05
Gain (termi-
nal AM)
Set the voltage level gain for
multi-function analog out-
put 2.
Set the number of multiples
of 10 V to be output as the
100% output for the monitor
items. The maximum output
from the terminal is 10 V.
A meter calibration function
is available.
*
0.00 to
2.50
0.50
Yes
Q
Q
Q
Q
421H
4-6
6-91
H4-06
Bias (termi-
nal AM)
Sets the multi-function ana-
log output 2 voltage level
bias.
Sets output characteristic up/
down parallel movement as a
percentage of 10 V.
The maximum output from
the terminal is 10 V.
A meter calibration function
is available.
*
-10.0 to
+10.0
0.0%
Yes
A
A
A
A
422H 6-92