Setting Inverter Input Voltage
Set the Inverter input voltage correctly in E1-01 to match the power supply voltage. This set value will be the
standard value for the protection function and similar functions.
The overvoltage detection level (OV) and the braking transistor operation level (BTR) vary depending on the
input voltage as shown in the following table.
E1-04
Max. output
frequency
To set V/f characteristics in a
straight line, set the same values for
E1-07 and E1-09. In this case, the
setting for E1-08 will be disre-
garded.
Always ensure that the four frequen-
cies are set in the following manner:
E1-04 (FMAX)
≥
E1-06 (FA) > E1-
07 (FB)
≥
E1-09 (FMIN)
40.0 to
400.0
*6
60.0 Hz
*2
No
Q
Q
Q
Q
303H
40.0 to
300.0
*5
E1-05
Max.
voltage
0.0 to
255.0
*1
200.0
V
*1*2
No
Q
Q
Q
Q
304H
E1-06
Base
frequency
0.0 to
400.0
*6
60.0 Hz
*2
No
Q
Q
Q
Q
305H
0.0 to
300.0
*5
E1-07
Mid. output
frequency
0.0 to
400.0
*6
3.0 Hz
*2
No
A
A
A
No
306H
0.0 to
300.0
*5
E1-08
Mid. output
frequency
voltage
0.0 to
255
*1
15.0 V
*1 *2
No
A
A
A
No
307H
E1-09
Min. output
frequency
0.0 to
400.0
*6
1.5 Hz
*2
No
Q
Q
Q
A
308H
0.0 to
300.0
*5
E1-10
Min. output
frequency
voltage
0.0 to
255.0
*1
9.0 V
*1 *2
No
A
A
A
No
309H
E1-11
Mid. output
frequency 2
Set only to fine-adjust V/f for the
output range. Normally, this setting
is not required.
0.0 to
400.0
*6
0.0 Hz
*3
No
A
A
A
A
30AH
0.0 to
300.0
*5
E1-12
Mid. output
frequency
voltage 2
0.0 to
255.0
*1
0.0 V
*3
No
A
A
A
A
30BH
E1-13
Base
voltage
0.0 to
255.0
*1
0.0 V
*4
No
A
A
Q
Q
30CH
Con-
stant
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
Output voltage (V)
Frequency (Hz)