Protective and Diagnostic Functions
This section describes the alarm functions of the Inverter. The alarm functions include fault detection,
alarm detection, operation error detection, and autotuning error detection.
Fault Detection
When the Inverter detects a fault, the fault contact output operates, and the Inverter output is shut OFF causing
the motor to coast to a stop. (The stopping method can be selected for some faults, and the selected stopping
method will be used with these faults.) A fault code is displayed on the Digital Operator.
When a fault has occurred, refer to the following table to identify and correct the cause of the fault.
Be sure to turn Run Command to OFF first, use one of the following methods to reset the fault before restart-
ing the Inverter.
•
Set a multi-function contact input (H1-01 to H1-06) to 14 (Fault Reset) and turn ON the fault reset signal.
•
Press the RESET Key on the Digital Operator.
•
Turn the main circuit power supply OFF and then ON again.
Table 7.1 Fault Displays and Processing
Display
Meaning
Probable Causes
Corrective Actions
Overcurrent
The Inverter output current exceeded
the overcurrent detection level. (200%
of rated current)
• A short-circuit or ground fault
occurred at the Inverter output. (A
short or ground fault can be caused
by motor burn damage, worn insu-
lation, or a damaged cable.)
• The load is too large or the accelera-
tion/deceleration time is too short.
• A special-purpose motor or motor
with a capacity too large for the
Inverter is being used.
• A magnetic contactor was switched
at the Inverter output.
Reset the fault after correcting its
cause.
Note) Before turning the power
ON again, make sure that no
short-circuit or ground fault
occurs at the Inverter output.
• A short-circuit bV,
−
V, and
AC terminals occurred.
• Overload in the control circuit ter-
minal.
• Make sure that incorrect wiring
has not been done.
• Check the resistance and wir-
ing for the frequency setting
potentiometer, etc. (Check that
the current for terV and
–V is 20 mA or less.)
Ground Fault
*
The ground fault current at the
Inverter output exceeded approxi-
mately 50% of the Inverter rated out-
put current.
A ground fault occurred at the Inverter
output. (A ground fault can be caused
by motor burn damage, worn insula-
tion, or a damaged cable.)
Reset the fault after correcting its
cause.
Note) Before turning the power
ON again, make sure that no
short-circuit or ground fault
occurs at the Inverter output.
• A short-circuit bV,
−
V, and
AC terminals occurred.
• Overload in the control circuit ter-
minal.
• Make sure that incorrect wiring
has not been done.
• Check the resistance and wir-
ing for the frequency setting
potentiometer, etc. (Check that
the current for terV and
–V is 20 mA or less.)
* The ground fault here is one which occurs in the motor wiring while the motor is running. A ground fault may not be detected in the following cases.
y
A ground fault with low resistance which occurs in motor cables or terminals.
y
A ground fault occurs when the power is turned ON.