![YASKAWA CIMR-F7A Скачать руководство пользователя страница 152](http://html1.mh-extra.com/html/yaskawa/cimr-f7a/cimr-f7a_instruction-manual_3214306152.webp)
5
-42
Analog Monitor Boards: F4
User constants for the Analog Monitor Board are shown in the following table.
* The CH1 output can be adjusted when the F4-02 or F4-05 setting is displayed in Quick, Advanced, or Verify mode while the motor is stopped.
The CH2 output can be adjusted when the F4-04 or F4-06 setting is displayed in Quick, Advanced, or Verify mode while the motor is stopped.
For analog output, the value equivalent to 100% of output value of monitored item is multiplied by the gain setting and the set bias is added.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
F4-01
Channel 1
monitor
selection
Effective when the Analog
Monitor Board is used.
Monitor selection:
Set the number of the moni-
tor item to be output. (U1-
)
The monitor items that can
be set depends on the control
method.
Gain:
Set the multiple of 10 V for
outputting monitor items.
4, 10 to 14, 25, 28, 31, 34,
35, 39, 40, 42 cannot be set.
29 to 31 are not used. When
the AO-12 Analog Monitor
Board is used, outputs of ±
10 V are possible. To output
± 10 V, set F4-07 or F4-08 to
1. When the AO-08 Analog
Monitor Board is used, only
outputs of 0 to +10 V are
possible.
A meter calibration function
is available.*
1 to 99
2
No
A
A
A
A
391H 6-92
F4-02
Channel 1
gain
0.00 to
2.50
1.00
Yes
A
A
A
A
392H 6-92
F4-03
Channel 2
monitor
selection
1 to 99
3
No
A
A
A
A
393H 6-92
F4-04
Channel 2
gain
0.00 to
2.50
0.50
Yes
A
A
A
A
394H 6-92
F4-05
Channel 1
output mon-
itor bias
Sets the channel 1 item bias
to 100%/10 V when the Ana-
log Monitor Board is used.
-10.0 to
10.0
0.0%
Yes
A
A
A
A
395H 6-92
F4-06
Channel 2
output mon-
itor bias
Sets the channel 2 item bias
to 100%/10 V when the Ana-
log Monitor Board is used.
-10.0 to
10.0
0.0%
Yes
A
A
A
A
396H 6-92
F4-07
Analog out-
put signal
level for
channel 1
0: 0 to 10 V
1: -10 to +10 V
0 or 1
0
No
A
A
A
A
397H 6-92
F4-08
Analog out-
put signal
level for
channel 2
0: 0 to 10 V
1: -10 to +10 V
0 or 1
0
No
A
A
A
A
398H 6-92