No.
Parameter Name
Setting Range
Default
F6-56
DeviceNet Speed Scaling
-15 to 15
0
F6-57
DeviceNet Current Scaling
-15 to 15
0
F6-58
DeviceNet Torque Scaling
-15 to 15
0
F6-59
DeviceNet Power Scaling
-15 to 15
0
F6-60
DeviceNet Voltage Scaling
-15 to 15
0
F6-61
DeviceNet Time Scaling
-15 to 15
0
Setting
The monitor value in the AC/DC Drive Object 2AH is calculated by:
AC/DC Drive Object 2AH Monitor = Drive Value × 2
Scaling
Example:
If the drive output frequency monitor (U1-02) is 5.00 and the scaling is set to F6-56 = 6, then the value in the AC/DC Drive
Object 2AH, Instance 1, Attribute 7 would be 500 × 2
6
= 32000.
n
F6-62: DeviceNet Heartbeat Interval
Sets the heartbeat interval for DeviceNet communications. A setting of 0 disables the heartbeat function.
No.
Parameter Name
Setting Range
Default
F6-62
DeviceNet Heartbeat Interval
0 to 10
0
n
F6-63: DeviceNet Network MAC ID
Displays the MAC ID assigned to the drive. F6-63 is used only as a monitor.
No.
Parameter Name
Setting Range
Default
F6-63
DeviceNet Network MAC ID
0 to 63 (read only)
0
n
F6-64 to F6-71: Dynamic Assembly Parameters (Reserved)
1.6 F: Option Settings
94
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual