Setting 10: Minor Fault
The output closes when a minor fault condition is present.
Setting 11: Fault Reset Command Active
The output closes when there is an attempt to reset a fault situation from the control circuit terminals, via serial communications,
or using a communications option card.
Setting 12: Timer Output
This setting configures a digital output terminal as the output for the timer function.
Refer to b4: Timer Function on page
for details.
Setting 13: Speed Agree 2 (f
ref
/f
out
Agree 2)
The output closes when the actual output frequency or motor speed (CLV, CLV/PM) is within the speed agree width (L4-04)
of the current frequency reference, regardless of the direction.
Status
Description
Open
Output frequency or motor speed does not match the frequency reference while the drive is running.
Closed
Output frequency or motor speed is within the range of frequency reference ±L4-04.
Note:
Detection works in forward and reverse.
L4-04
L4-04
Frequency
reference
Speed Agree 2
ON
OFF
Output Frequency
or Motor Speed
Figure 1.68 Speed Agree 2 Time Chart
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 145
Setting 14: User-Set Speed Agree 2 (f
ref
/f
set
Agree 2)
The output closes when the actual output frequency or motor speed (CLV, CLV/PM) and the frequency reference are within
the speed agree width (L4-04) of the programmed speed agree level (L4-03).
Status
Description
Open
Output frequency or motor speed and frequency reference are both outside the range of L4-03 ±L4-04.
Closed
Output frequency or motor speed and the frequency reference are both within the range of L4-03 ±L4-04.
Note:
The detection level L4-03 is a signed value; detection works in the specified direction only.
1.7 H: Terminal Functions
110
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual