No.
Name
Setting Range
Default
L2-05
Undervoltage Detection Level
300 to 420 Vdc
Determined by
A1-02, C6-01, E1-01
and o2-04
Note:
1.
Install an AC reactor option on the input side of the power supply when setting L2-05 below the default value to prevent damage to
drive circuitry.
2.
If using KEB Ride-Thru and L2-05 is set too low, then undervoltage in the DC bus (Uv1) will be triggered before KEB Ride-Thru can
be executed. Take caution not to set this value too low.
n
L2-07: KEB Acceleration Time
Sets the time to reaccelerate from the speed when KEB was deactivated to the frequency reference.
When set to 0.0 s, the drive will accelerate to speed according to the active acceleration time set by C1-01, C1-03, C1-05, or
C1-07.
No.
Name
Setting Range
Default
L2-07
KEB Acceleration Time
0.00 to 6000.0 s
0.00 s
n
L2-10: KEB Detection Time (Minimum KEB Time)
Determines the duration of KEB Ride-Thru operation after it is triggered.
Refer to KEB Ride-Thru End Detection on page
for details.
No.
Name
Setting Range
Default
L2-10
KEB Detection Time
0 to 2000 ms
50 ms
n
L2-11: DC Bus Voltage Setpoint during KEB
Determines the setpoint (target value) for the DC bus voltage during Single KEB Ride-Thru 2. For Single KEB Ride-Thru 1
and System KEB Ride-Thru, parameter L2-11 defines the voltage level to end KEB Ride-Thru.
No.
Name
Setting Range
Default
L2-11
DC Bus Voltage Setpoint during KEB
Determined by
E1-01
u
L3: Stall Prevention
The motor may experience excessive slip because it cannot keep up with the frequency reference when the load is too high or
acceleration and deceleration times are too short. If the motor slips during acceleration, it usually causes an overcurrent fault
(oC), drive overload (oL2), or motor overload (oL1). If the motor slips during deceleration, it can cause excessive regenerative
power to flow back into the DC bus capacitors, and eventually cause the drive to fault out from overvoltage (ov). The Stall
Prevention Function prevents the motor from stalling and while allowing the motor to reach the desired speed without requiring
the user to change the acceleration or deceleration time settings. The Stall Prevention function can be set separately for
acceleration, operating at constant speeds, and deceleration.
n
L3-01: Stall Prevention Selection during Acceleration
Stall Prevention during acceleration prevents tripping with overcurrent (oC), motor overload (oL1), or drive overload (oL2)
faults common when accelerating with heavy loads.
L3-01 determines the type of Stall prevention the drive should use during acceleration.
No.
Name
Setting Range
Default
L3-01
Stall Prevention Selection during Acceleration
0 to 2
1
<1> Setting 2 is not available for OLV/PM.