n
H3-14: Analog Input Terminal Enable Selection
When one of the multi-function digital input parameters is set for “Analog input enable” (H1-
oo
= C), the value set to H3-14
determines which analog input terminals are enabled when the input is closed. All of the analog input terminals will be enabled
all of the time when H1-
oo
≠
C. The terminals not set as the target are not influenced by input signals.
No.
Name
Setting Range
Default
H3-14
Analog Input Terminal Enable Selection
1 to 7
7
Setting 1: A1 Only Enabled
Setting 2: A2 Only Enabled
Setting 3: A1 and A2 Only Enabled
Setting 4: A3 Only Enabled
Setting 5: A1 and A3 Only Enabled
Setting 6: A2 and A3 Only Enabled
Setting 7: All Analog Input Terminals Enabled
n
H3-16 to H3-18: Terminal A1/A2/A3 Offset
Set the offset level of the selected input value to terminals A1, A2, or A3 that is equal to 0 Vdc input. These parameters rarely
require adjustment.
No.
Name
Setting Range
Default
H3-16
Terminal A1 Offset
-500 to 500
0
H3-17
Terminal A2 Offset
-500 to 500
0
H3-18
Terminal A3 Offset
-500 to 500
0
n
Multi-Function Analog Input Terminal Settings
for information on how H3-02, H3-10, and H3-06 determine functions for terminals A1, A2, and A3.
Note:
The scaling of all input functions depends on the gain and bias settings for the analog inputs. Set these to appropriate values when selecting
and adjusting analog input functions.
Table 1.41 Multi-Function Analog Input Terminal Settings
Setting
Function
Page
0
Frequency Bias
1
Frequency Gain
2
Auxiliary Frequency Reference 1
3
Auxiliary Frequency Reference 2
4
Output Voltage Bias
5
Accel/Decel Time Gain
6
DC Injection Braking Current
7
Torque Detection Level
8
Stall Prevention Level During Run
9
Output Frequency Lower Limit Level
B
PID Feedback
C
PID Setpoint
D
Frequency Bias
E
Motor Temperature (PTC Input)
Setting
Function
Page
F
Through Mode
10
Forward Torque Limit
11
Reverse Torque Limit
12
Regenerative Torque limit
13
Torque Limit Using Torque Reference/Speed Limit
14
Torque Compensation
15
General Torque Limit
16
Differential PID Feedback
Motor Thermistor (NTC)
1F
Through Mode
30
DriveWorksEZ Analog Input 1
31
DriveWorksEZ Analog Input 2
32
DriveWorksEZ Analog Input 3
<1> This function is available in models CIMR-A
4A0930 to 4A1200 and A1000 HHP.
Setting 0: Frequency Bias
The input value of an analog input set to this function will be added to the analog frequency reference value. When the frequency
reference is supplied by a different source other than the analog inputs, this function will have no effect. Use this setting also
when only one of the analog inputs is used to supply the frequency reference.
1.7 H: Terminal Functions
118
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual