Register No.
Contents
000FH
Control Selection Setting
bit 0
Reserved
bit 1
PID Setpoint Input
bit 2
Torque reference / torque limit input (enables the setting from MEMOBUS/Modbus)
bit 3
Torque compensation input (enables the setting from MEMOBUS/Modbus)
bit 4 to B
Reserved
bit C
Enable Terminal S5 Input for Broadcast Data
bit D
Enable Terminal S6 Input for Broadcast Data
bit E
Enable Terminal S7 Input for Broadcast Data
bit F
Enable Terminal S8 Input for Broadcast Data
0010H to 001AH
Reserved
001BH
Analog Monitor Option AO-A3 Analog Output 1 (10 V/4000 H)
001CH
Analog Monitor Option AO-A3 Analog Output 2 (10 V/4000 H)
001DH
Digital Output Option DO-A3 Output (Binary)
001EH to 001FH
Reserved
u
Monitor Data
Monitor data can be read only.
Register No.
Contents
0020H
Drive Status 1
bit 0
During Run
bit 1
During Reverse
bit 2
Drive Ready
bit 3
Fault
bit 4
Data Setting Error
bit 5
Multi-Function Contact Output (terminal M1-M2)
bit 6
Multi-function Photocoupler output 1(Terminal P1 - PC(
bit 7
Multi-function Photocoupler output 2(Terminal P2 - PC(
bit 8 to bit D
Reserved
bit E
ComRef status
bit F
ComCtrl status
0021H
Fault Contents 1
bit 0
Overcurrent (oC), Ground fault (GF)
bit 1
Overvoltage (ov)
bit 2
Drive Overload (oL2)
bit 3
Overheat 1 (oH1), Drive Overheat Warning (oH2)
bit 4
Dynamic Braking Transistor Fault (rr), Braking Resistor Overheat (rH)
bit 5
Reserved
bit 6
PID Feedback Loss (FbL / FbH)
bit 7
EF to EF8: External Fault
bit 8
CPF
oo
: Hardware Fault (includes oFx)
bit 9
Motor Overload (oL1), Overtorque Detection 1/2 (oL3/oL4), Undertorque Detection 1/2 (UL3/
UL4)
bit A
PG Disconnected (PGo), PG Hardware Fault (PGoH), Overspeed (oS), Excessive Speed Deviation
(dEv)
bit B
Main Circuit Undervoltage (Uv)
bit C
Undervoltage (Uv1), Control Power Supply Undervoltage (Uv2), Soft Charge Circuit Fault (Uv3)
bit D
Output Phase Loss (LF), Input Phase Loss (PF)
bit E
MEMOBUS/Modbus Communication Error (CE), Option Communication Error (bUS)
bit F
Operator Connection Fault (oPr)