![YASKAWA A1000 HHP Скачать руководство пользователя страница 272](http://html1.mh-extra.com/html/yaskawa/a1000-hhp/a1000-hhp_programming-manual_3232370272.webp)
H1 Multi-Function Digital Input Selections
H1-
oo
Setting
Function
Description
Page
35
PID input level selection
All Modes
Closed: Inverts the PID input signal.
40
Forward run command
(2-Wire sequence)
All Modes
Open: Stop
Closed: Forward run
Note:
Cannot be set together with settings 42 or 43.
41
Reverse run command
(2-Wire sequence)
All Modes
Open: Stop
Closed: Reverse run
Note:
Cannot be set together with settings 42 or 43.
42
Run command
(2-Wire sequence 2)
All Modes
Open: Stop
Closed: Run
Note:
Cannot be set together with settings 40 or 41.
43
FWD/REV command
(2-Wire sequence 2)
All Modes
Open: Forward
Closed: Reverse
Note:
Determines motor direction, but does not issue a Run command. Cannot be set
together with settings 40 or 41.
44
Offset frequency 1
All Modes
Closed: Adds d7-01 to the frequency reference.
45
Offset frequency 2
All Modes
Closed: Adds d7-02 to the frequency reference.
46
Offset frequency 3
All Modes
Closed: Adds d7-03 to the frequency reference.
47
Node setup
All Modes
Closed: Node setup for SI-S3 enabled.
60
DC Injection Braking command
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
Closed: Triggers DC Injection Braking.
61
External Speed Search
command 1
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
OLV/PM
AOLV/PM
OLV
Closed: Activates Current Detection Speed Search from the maximum output frequency
(E1-04).
62
External Speed Search
command 2
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
OLV/PM
AOLV/PM
OLV
Closed: Activates Current Detection Speed Search from the frequency reference.
63
Field weakening
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
V/f w PG
Closed: The drive performs Field Weakening control as set for d6-01 and d6-02.
65
KEB Ride-Thru 1 (N.C.)
All Modes
Open: KEB Ride-Thru 1 enabled.
66
KEB Ride-Thru 1 (N.O.)
All Modes
Closed: KEB Ride-Thru 1 enabled.
67
Communications test mode
All Modes
Tests the MEMOBUS/Modbus RS-485/422 interface. Displays “PASS” if the test completes
successfully.
6A
Drive enable
All Modes
Open: Drive disabled. If this input is opened during run, the drive will stop as specified by
b1-03.
Closed: Ready for operation.
A.9 H Parameters: Multi-Function Terminals
272
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual