WS009568A
1. Enter the Resistivity, Length of sensor cable, and Wire cross section under Calculation
help for lead resistance.
2. Select Shared return lead for sensors that use a common return lead.
3. Click Calculate.
The calculated value is entered automatically in the Lead resistance.
4. Click Update.
6.8.9 Set the reload time for alarm and quick overview
1. Click Setup > General configuration > General settings.
2. Select the reload time.
The default is one minute. This time is the interval to update the measurements results
and alarms that are shown on the Quick overview and Alarm and event log pages.
6.8.10 Set up the email account for alarm notification
1. Click Setup > General configuration > Email settings.
WS009571A
2. Enter a valid Sender address.
3. Enter the SMTP server name and the SMTP port number.
The default SMTP port number is 25.
4. Select the MIME encoding.
6 System Setup
MAS 711 Installation, Operation, and Maintenance Manual
29