PAGE 9
Aquavar IPC Start-Up Genie
CentriPro
Install Transducer cable on:
✔
Brown on terminal 12 (24V)
✔
White on terminal 53 (4-20MA)
✔
Place ground shield between spring clip
and shielded cable.
Install Jumper wires on:
✔
Terminal 12 and 18
The IPC has been configured to require a
start command on terminal 18. To apply
a start signal connect a jumper wire
between terminals 18 (DI 18, parameter
5-10) and 12 (24V dc). A start command
is given to the controller when terminal
18 is connected to 24V.
✔
Terminal 29 and 32
This jumper allows the drive to
automatically restart in the event of a no
water loss of prime.
SINGLE PUMP CONTROL WIRING