PAGE 19
Aquavar IPC Start-Up Genie
CentriPro
NO FLOW POWER CALIBRATION
The No Flow Power Calibration Setup
provides the method to program the no flow
power curve in to the controller
- In order to detect a no flow condition for
the various pump(s), the no flow power
curve needs to be programmed in to the
drive
Select Quick Menu
Select 04* Startup Genie
Change Setup Selection to Pump Protection.
Select Enable for sleep mode.