PAGE 10
Aquavar IPC Start-Up Genie
CentriPro
✔
Check Pump and Motor Rotation by
selecting Hand On. If motor is running
backwards, power down drive, wait five
minutes, and rotate motor wires from the
drive. Once rotation is verified, select Off.
✔
Select Auto On. Verify Unit cycles into
sleep mode at desired PSI.