PAGE 24
Aquavar IPC Start-Up Genie
CentriPro
AQUAVAR® INTELLIGENT PUMP CONTROLLER START-UP GENIE PARAMETERS (IM287)
The Start-Up Genie is the fastest way to accurately program an IPC. However, when fine tuning is
required, users may use the parameters in the main menu of the IPC. The table below is a cross
reference between the Genie settings and their corresponding parameters in the main menu.
IPC GENIE MENU SCREEN:
• Motor:
• Motor Power (HP): 1-21
• Motor Voltage: 1-22
• Motor Frequency: 1-23
• Motor Nominal Speed: 1-25
• Motor Current: 1-24
• Current Limit: 4-18
• Motor Type:
❍
Surface:
– Sleep Frequency/Low Limit: 4-12
❍
Submersible:
– Sleep Frequency/Low Limit: 4-12
• Operating Mode:
• Single Pump:
(continue on Application Type)
• Constant Slave:
(Note: Pump 1 is the one for variable speed)
❍
Number of Pumps: 25-06 (2 or 3)
– Two Pumps: 05-4 R1 (for fixed-speed Pump 1)
– Three Pumps: 05-4 R2 (for fixed-speed Pump
2) and 540.1 (for fixed-speed P3)
❍
Run Time Equalization: 25-04
❍
Staging Bandwidth: 25-20
❍
SBW Staging Delay: 25-23
❍
SBW Destaging Delay: 25-24
• Duplex Control:
❍
Duty Standby: 5-13, 5-31
❍
Lag pump start frequency: 5-4* (5-40.0, 5-40.1)
(5-41.0, 5-41.1)
❍
Alternation: 25-50, Smart Logic (13-44.0)
❍
Alternation Time: 25-52, Smart Logic (13-20.0)
❍
Pump Exercise Time: 22-40
❍
Start Delay: 1-71
• Speed Control:
❍
Speed Reference Source: 6-** (Select the AI
(53 or 54) you want to use and (Volts or Amps)
– Terminal 53 Low Ref./Feedback: 6-14
– Terminal 53 High Ref./Feedback: 6-15
– Min Speed Reference: 3-02
– Max Speed Reference: 3-03
• Test Run Mode: 5-10 [14] Jog
❍
Test Run Speed: 3-11
❍
Test Run Ramp Time: 3-80
• Application Type:
• Level Control:
❍
Level control units: 20-12,20-05,20-08
❍
Tank Fill or Tank Empty Application:
– Fill: 20-81 (PID Normal)
– Empty: 20-81 (PID Inverse)
– Ramp Time: 3-41, 3-42, 3-52
• Flow Control:
❍
Level control units: 20-12
❍
Ramp Time: 3-41 and 3-42
• Constant Pressure:
❍
Pressure Control Units: 20-12
❍
Ramp Time: 3-41, 3-42, 3-51, 3-52
• *Autoset: *Would you Like to Autoset the rest of
the setting? (Calculation Values):
• Setpoint 1: 20-21 (50 psi)
• Wake-up Ref./FB Difference: 22-44 = (5/20-
21)*100 (for Constant Pressure, Level Control and
Duplex Control)
• Low Speed [Hz]: 22-33 = 4-14*0.5
• High Speed [Hz]: 22-37 = 4-14*0.85
• Low Speed Power [HP]: 22-35 = 22-39* (22-33 /
4-14)^3
• High Speed Power [HP]: 22-39 = 1-21*4-18*0.46