PAGE 15
Aquavar IPC Start-Up Genie
CentriPro
DUPLEX PROGRAMMING
Select Yes to Autoset the rest of the settings.
For Duplex configuration here are the
parameters that will get autoset:
Duplex Autoset Configuration Constant Pressure
Transducer Max Feedback
300 [unit]
Transducer Type
4-20mA
Feedback 1 Source
AI 53
Sleep Frequency
30 Hz
Restart Difference
5 [unit]
No Water/Loss of Prime Fault
Enabled
Duty Standby
Disabled
Lag Start Frequency
59 Hz
Lag Stop Frequency
35 Hz
Alternation
Enabled
Alternation Time
24 Hrs
Pump Exercise Time
0 s (Disabled)
✔
Select Set point PSI
Cycle through these three screens and then
press OK.
You can now power off both drives and
prepare control wiring between the two
drives.