PAGE 29
Aquavar IPC Start-Up Genie
CentriPro
• Install Jumper to run wire on Terminal #12 and #18
on both drives
• Install Transducer Cable: White on #53, Brown on
#12
•
BLUE
: Drive 1 Analog I/O #42 to Drive 2 Analog I/O
#54
•
YELLOW
: Drive 1 Analog I/O #54 to Drive 2 Analog
I/O #42
•
VIOLET
: Drive 1 Digital I/O #13 to Drive 1 Relay 2
#04 (Internal Jumper)
•
RED
: Drive 1 Digital I/O #27 to Drive 2 Relay 2 #05
FINAL DUPLEX WIRING DIAGRAM
• BLACK: Drive 1 Relay #2 05 to Drive Digital #27
•
WHITE
: Drive 1 Digital I/O #20 to Drive 2 Digital I/O
#20
•
GREEN
: Drive 1 Digital I/O #29 to Drive 2 Digital I/O
#32
•
BROWN
: Drive 1 Digital I/O #32 to Drive 2 Digital
I/O #29
•
ORANGE
: Drive 2 Digital I/O #13 to Drive 2 Relay 04
(Internal Jumper)
Drive 1
Drive 2
YELLOW
BROWN
BROWN
BLUE
WHITE
WHITE
WHITE
GREEN
BROWN
VIOLET
JUMPER TO
RUN
JUMPER
TO RUN
BLACK
ORANGE
RED
Analog I/O
39
42
50
53
54
55
COM A OUT +10V A IN A IN COM
Digital I/O
12
13
18
19
27
29
32
33
20
+24V +24V D IN D IN D IN D IN D IN D IN COM
Relay 2
04
05
06
COM NO
NC
Relay 2
04
05
06
COM NO
NC
Digital I/O
12 13 18 19 27 29 32 33 20
+24V +24V D IN D IN D IN D IN D IN D IN COM
Analog I/O
39
42
50
53
54
55
COM A OUT +10V A IN A IN COM