XC series analog expansions User Manual Page 13 of 53
MANU003R2V1
Expansion’s 0CH - 3CH channels have two modes to select: voltage 0-5V, 0-10V, 4CH - 7CH
channels have two modes to select, current 0-20mA, 4-20mA. Set via special FLASH data
register FC inside PLC. See the following table:
Module
Channel’s ID
0CH-3CH
4CH-7CH
1# module
FD8250
FD8251
2# module
FD8258
FD8259
3# module
FD8266
FD8267
4# module
FD8274
FD8275
5# module
FD8282
FD8283
6# module
FD8290
FD8291
7# module
FD8298
FD8299
Note:
As shown in the preceding table, each register sets 4 channels’, each register has 16 bits. From
low bit to high bit, every 4 bits separately sets 4 channels.
Each bit’s definition is shown in the following table:
3-3 Working mode settings
Take 1# module as example:
FD8250 H O O O O
0CH
1CH
2CH
3CH
FD8251 H O O O O
4CH
5CH
6CH
7CH