XC series analog expansions User Manual Page 27 of 53
MANU003R2V1
Register FD8251 low byte:
E.g. 1
If set working mode 0-20mA / 4-20mA, 0-10V / 0-5V filters are all 1/2 filter, value in
FD8250 is 2301H
When connecting 24V power, use 24V power on PLC main unit to avoid interference.
To avoid interference, use shielded cable and single point grounding with the shield.
Module’s 0-20mA or 4-20mA output need 24V external power, the module adjusts the loop
circuit’s current, but the module itself doesn’t produce current.
Channel 5
Channel 4
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
00
:
1/2 filter
01
:
no filter
10
:
1/3 filter
11
:
1/4 filter
0
:
voltage
input
0
:
0~10V
1
:
0~5V
00
:
1/2 filter
01
:
no filter
10
:
1/3 filter
11
:
1/4 filter
0
:
voltage
input
0
:
0~10V
1
:
0~
5V
1
:
current
input
0
:
0~20mA
1
:
4~20mA
1
:
current
input
0
:
0~20m
A
1
:
4~
20m
A