XC series analog expansions User Manual Page 25 of 53
MANU003R2V1
Register’s ID of expansion 7:
Channel
AD signal
PID output
value
PID start/stop
control bit
The set
value
PID
parameters
Kp, Ki, Kd,
control band
Diff, dead
band
0CH
ID700
ID704
Y700
QD702
Kp: QD706
Ki: QD707
Kd: QD708
Diff: QD709
Dead: QD710
1CH
ID701
ID705
Y701
QD703
2CH
ID702
ID706
Y702
QD704
3CH
ID703
ID707
Y703
QD705
Channel
DA signal
-
-
-
-
4CH
QD700
-
-
-
5CH
QD701
-
-
-
Description
Start signal: When Y is 0, stop PID control; when is 1, start PID control
a.) Parameter P is the proportional parameter, acts on the difference between the actual process
value and the target value.
b.) Parameter I is integral parameter, used to remove the offset.
c.) Parameter D is derivative parameter, mainly used to control signal’s changing trend speed.
Each parameter’s reference value: Kp=20 to 100, Ki=5 to 20, Kd=200 to 700, DIFF=100 to 200