Relay Timing
C–2
975-0307-01-01
RunMode
For generators with RunMode starting types (Types 7 and 8):
•
Relay 1 (RunStop relay) can be used for two-wire configured
generators.
•
Relay 1 (RunStop) and Relay 2 (Start) can be used with a common
ground for three-wire configured generators.
•
The Preheat will never overlap the Crank Time.
•
The “Delay” refers to the “Preheat to Crank Delay” and may be zero.
•
Cranking will cease when the generator run signal goes high for the
specified hold time or when the crank time has elapsed.
Figure C-1
RunMode Timing Diagram