Installing the XW Automatic Generator Start
975-0307-01-01
2–17
Type 9
Type 9 is a StartStop mode configuration with shutdown bypass
functionality on relay 3. This configuration is intended for Westerbeke
generators.
Figure 2-13
Type 9 Connection Diagram
For additional information, see
“Circuit Limitations” on page 2–5.
XW AGS Harness Wires
Generator Wires
18
17
16
14
13
12
20
19
FUEL PRIME (PREHEAT)
12V GENERATOR B
Relay 1
Relay 3
Relay 2
5A fuse
5A fuse
5A fuse
GENERATOR RUN SIGNAL
STOP
START
GENERATOR BATTERY NEGATIVE (–)
Table 2-12
Type 9 Relay and Timing Preset Configurations
Relay Function
Preset Configuration Setting
Relay 1 mode
StartStop
Relay 3 mode
Shutdown Bypass
Gen Run signal hold time
0.5 s
Preheat time
0 s
Preheat to crank delay
0 s
Crank time
15 s
Crank retry time
30 s
Gen Cool Down
30 s
Shutdown bypass time
5 s
Start tries
3